28 Pa. Code § 205.62. Special heating requirements for new construction.

§ 205.62. Special heating requirements for new construction.

 (a)  Boiler feed pumps, heat circulating pumps, condensate return pumps and fuel oil pumps shall be connected and installed so that the total load can be carried by the remaining pumps with one pump out of service.

 (b)  To prevent shutting down the entire system when repairs are required, supply and return mains and risers of cooling, heating and process steam systems shall be valved to isolate the various sections of the system. Each piece of equipment shall be valved at the supply and return.

Authority

   The provisions of this §  205.62 amended under section 803 of the Health Care Facilities Act (35 P. S. §  448.803); and section 2102(g) of The Administrative Code of 1929 (71 P. S. §  532(g)).

Source

   The provisions of this §  205.62 adopted August 29, 1975, effective September 1, 1975, 5 Pa.B. 2233; amended January 31, 1987, effective July 1, 1987, 17 Pa.B. 514; amended July 23, 1999, effective July 24, 1999, 29 Pa.B. 3999. Immediately preceding text appears at serial page (242529).