[Continued from previous Web Page] (D) After analyses of four consecutive quarterly samples at an entry point, including initial quarterly samples, demonstrate that the VOC levels in each quarterly sample are less than the MCLs, the required monitoring is reduced to one sample per year at the entry point for the VOCs for which the EPA has established MCLs under 40 CFR 141.61(a), except for vinyl chloride as provided in subparagraph (i).
(E) A confirmation sample shall be collected and analyzed for each VOC listed under 40 CFR 141.61(a) which is detected at a level in excess of its MCL during annual or less frequent compliance monitoring. The confirmation sample shall be collected within 2 weeks of notification by the certified laboratory performing the analysis that an MCL has been exceeded. The average of the results of the original and the confirmation sample will be used to determine compliance. Monitoring shall be completed by the deadline specified for VOC compliance monitoring.
(iv) Repeat monitoring for entry points at which no VOC is detected.
(A) For entry points at which VOCs are not detected during the first year of quarterly monitoring, or annual monitoring if only one sample was required at an entry point for first year monitoring under subparagraph (ii) (E), (F) or (G)(II), required monitoring is reduced to one sample per entry point per year.
(B) For groundwater entry points where VOCs are monitored in accordance with this paragraph, but are not detected during 3 years of quarterly or annual monitoring, or both, required monitoring is reduced to one sample per entry point during each subsequent compliance period. Reduced monitoring shall be conducted at 3-year intervals from the year of required initial monitoring.
(v) Reduced monitoring. When reduced monitoring is provided under subparagraph (iii)(D), or subparagraph (iv)(A) or (B), the system shall monitor the entry point during the calendar year quarter of highest anticipated VOC levels or as specified by the Department. The reduced monitoring option in subparagraph (iv)(B) does not apply to entry points at which treatment has been installed for VOC removal. Quarterly performance monitoring is required for VOCs for which treatment has been installed.
(vi) Waivers. Waivers under 40 CFR 141.24(f) will not be available for the VOC monitoring requirements in this paragraph.
(6) Monitoring requirements for SOCs (pesticides and PCBs). Community water systems and nontransient noncommunity water systems shall monitor for compliance with the MCLs for SOCs established by the EPA under 40 CFR 141.61(c). The monitoring shall be conducted according to the requirements established by the EPA under 40 CFR 141.24(h), incorporated herein by reference except as modified by this chapter.
(i) Initial monitoring schedule. Initial monitoring shall consist of four consecutive quarterly samples at each entry point beginning during the quarter beginning January 1, 1995, except for systems which are granted an initial monitoring waiver in accordance with subparagraph (v). Systems which monitor during the initial monitoring period but begin monitoring before 1995 shall begin monitoring during the first calendar quarter of the year.
(A) New entry points associated with new sources which are vulnerable to SOC contamination, as determined in accordance with subparagraph (v), and which begin operation after March 31, 1995, and do not detect an SOC during new source sampling shall begin initial quarterly monitoring during the first calendar year quarter of the year after the entry point begins serving the public.
(B) New entry points associated with new sources which are vulnerable to SOC contamination as determined in accordance with subparagraph (v), at which an SOC is detected during new source sampling shall begin initial quarterly monitoring the first quarter the entry point begins serving the public. Quarterly monitoring shall continue until reduced monitoring is granted in accordance with subparagraph (ii)(E).
(ii) Repeat monitoring for SOCs that are detected. For entry points which were monitored for SOCs during the initial quarterly monitoring period or during the required quarterly monitoring immediately after being determined vulnerable to contamination by an SOC, repeat monitoring shall be conducted as follows:
(A) For entry points at which an SOC is detected at a level equal to or greater than its MCL, the monitoring for the detected SOC shall be continued quarterly, until reduced monitoring is granted in accordance with clause (E).
(B) For entry points at which an SOC is detected during the first year of quarterly monitoring, and reduced monitoring is granted in accordance with clause (E), and the SOC is thereafter detected at a level greater than its MCL, the monitoring for the detected SOC shall be repeated quarterly, until reduced monitoring is granted in accordance with clause (E).
(C) For entry points at which an SOC is not detected during the first year of quarterly monitoring, but an SOC is detected initially thereafter at a level less than the MCL, monitoring shall be repeated annually for the detected SOC.
(D) For entry points at which an SOC is not detected during the first year of quarterly monitoring, but the SOC is detected thereafter at a level equal to or greater than the MCL, monitoring for that SOC shall be repeated quarterly, until reduced monitoring is granted in accordance with clause (E).
(E) After analyses of four consecutive quarterly samples at an entry point, including initial quarterly samples, demonstrate that the SOC level in each quarterly sample is less than the MCL, the required monitoring for each SOC detected below the MCL is reduced to one sample per year at the entry point.
(F) For entry points at which either heptachlor or heptachlor epoxide is detected during the initial round of consecutive quarterly samples, or in subsequent repeat samples, the monitoring shall be continued for both contaminants in accordance with the more frequent monitoring required of the two contaminants based on the level at which each is detected.
(G) A confirmation sample shall be collected and analyzed for each SOC listed under 40 CFR 141.61(c) which is detected at a level in excess of its MCL during annual or less frequent compliance monitoring. The confirmation sample shall be collected within 2 weeks of the water supplier receiving notification from the certified laboratory performing the analysis that an MCL has been exceeded. The average of the results of the original and the confirmation samples will be used to determine compliance. Confirmation monitoring shall be completed by the deadline specified for SOC compliance monitoring.
(iii) Repeat monitoring for SOCs that are not detected. For entry points at which SOCs are not detected during the first year of quarterly monitoring, the required monitoring is reduced to one sample in each 3-year compliance period for systems serving 3,300 or fewer persons and to two consecutive quarterly samples in each compliance period for systems serving more than 3,300 persons. Reduced monitoring shall be conducted at 3-year intervals from the year of required initial VOC monitoring, in accordance with paragraph (5)(ii).
(iv) Reduced monitoring. When reduced monitoring is provided under subparagraph (ii) or (iii), the system shall monitor the entry point during the second calendar year quarter, or the second and third calendar year quarter when two quarterly samples are required in each compliance period, unless otherwise specified by the Department. The reduced monitoring option in subparagraph (iii) does not apply to entry points at which treatment has been installed for SOC removal. Compliance monitoring for SOCs for which treatment has been installed to comply with an MCL shall be conducted at least annually, and performance monitoring shall be conducted quarterly.
(v) Waivers. A waiver will be granted to a public water supplier from conducting the initial compliance monitoring or repeat monitoring, or both, for an SOC based on documentation provided by the public water supplier and a determination by the Department that the criteria in clause (B), (C) or (D) has been met. A waiver is effective for one compliance period and may be renewed in each subsequent compliance period. If the Department has not granted an areawide use waiver in accordance with clause (B), the public water supplier is responsible for submitting a waiver application and renewal application to the Department for review in accordance with clause (B) or (C) for specific entry points. Waiver applications will be evaluated relative to the vulnerability assessment area described in clause (A) and the criteria in clause (B) or (C). Entry points at which treatment has been installed to remove an SOC are not eligible for a monitoring waiver for the SOCs for which treatment has been installed.
(A) Vulnerability assessment area for SOCs except dioxin and PCBs.
(I) For groundwater entry points, the vulnerability assessment area shall consist of wellhead protection area Zones I and II.
(II) For surface water entry points, the vulnerability assessment area shall consist of the area that supplies water to the entry point and is separated from other watersheds by the highest topographic contour.
(B) Use waivers. An areawide use waiver will be granted by the Department for contaminants which the Department has determined have not been used, stored, manufactured or disposed of in this Commonwealth, or portions of this Commonwealth. A use waiver specific to a particular entry point requires that an SOC was not used, stored, manufactured or disposed of in the vulnerability assessment area. If use waiver criteria cannot be met, a public water supplier may apply for a susceptibility waiver.
(C) Susceptibility waivers. A susceptibility waiver for specific contaminants may be granted based on the following criteria, and only applies to groundwater entry points:
(I) Previous analytical results.
(II) Environmental persistence and transport of the contaminant.
(III) Proximity of the drinking water source to point or nonpoint source contamination.
(IV) Elevated nitrate levels as an indicator of the potential for pesticide contamination.
(V) Extent of source water protection or approved wellhead protection program.
(D) Waivers for dioxin and PCBs. A system is granted a waiver from monitoring for dioxin and PCBs unless the Department determines that there is a source of dioxin or PCB contamination which poses a threat to a drinking water source.
(7) Monitoring requirements for IOCs. Community water systems and nontransient noncommunity water systems shall monitor for compliance with the MCLs for IOCs established by the EPA under 40 CFR 141.62 (relating to maximum contaminant levels (MCLs) for inorganic contaminants), and for arsenic established by the EPA under 40 CFR 141.11 (relating to maximum contaminant levels for inorganic contaminants). Transient noncommunity water suppliers shall monitor for compliance with the MCLs for nitrate and nitrite. The monitoring shall be conducted according to the requirements established by the EPA under 40 CFR 141.23 (relating to inorganic chemical sampling and analytical requirements). The requirements are incorporated by reference except as modified by this chapter.
(i) Monitoring requirements for asbestos.
(A) Waivers for asbestos monitoring. A system is granted a waiver from asbestos monitoring unless the Department determines that the system's distribution system contains asbestos cement pipe and the system has not implemented optimum corrosion control measures, or the Department determines that the system's source water is vulnerable to asbestos contamination.
(B) Initial monitoring schedule. Community water systems and nontransient noncommunity water systems not granted a waiver under clause (A) shall monitor for compliance with the MCL for asbestos by taking one sample at each vulnerable sampling point during the first 3-year compliance period of each 9-year compliance cycle, with the initial compliance monitoring beginning not later than the calendar year beginning January 1, 1995.
(C) Monitoring of new entry points. New entry points which begin operation after December 31, 1995, shall conduct initial monitoring during the first compliance period of the first compliance cycle after the entry point begins serving the public, if the Department determines that a waiver cannot be granted in accordance with clause (A).
(D) Repeat monitoring for systems that detect asbestos. If a sample exceeds the MCL for asbestos, the monitoring at that sampling point shall be continued quarterly beginning in the quarter following the MCL violation. After four consecutive quarterly samples less than the MCL at that entry point, the required monitoring is reduced to one sample at that entry point during the first 3-year compliance period of each subsequent 9-year compliance cycle, if treatment has not been installed to remove asbestos from the source water. Compliance monitoring at entry points at which treatment has been installed to remove asbestos from source water shall be conducted at least annually, and performance monitoring shall be conducted quarterly.
(ii) Monitoring requirements for nitrate and nitrite. The following compliance monitoring for nitrite is not required at entry points receiving water which has been disinfected with free chlorine, chlorine dioxide or ozone:
(A) Initial monitoring schedule. A public water system shall begin new monitoring for nitrate and nitrite by taking one annual sample at each groundwater entry point to the system beginning during the year beginning January 1, 1993. Community water systems and nontransient noncommunity water systems with surface water sources shall monitor quarterly at each surface water entry point for nitrate and nitrite beginning during the quarter beginning January 1, 1993. Transient noncommunity water systems shall monitor each surface water entry point by taking one annual sample beginning during the year beginning January 1, 1993.
(B) Monitoring of new entry points. New community and nontransient noncommunity surface water entry points which begin serving the public after the first calendar quarter of a year and did not detect levels of nitrate or nitrite equal to or greater than 50% of the MCL during new source sampling shall begin initial monitoring for nitrate and nitrite during the first calendar quarter of the year after the entry point begins serving the public. New community and nontransient noncommunity groundwater and surface water entry points at which nitrate or nitrite is detected at levels equal to or greater than 50% of the MCL during new source sampling shall begin initial quarterly monitoring the first quarter the entry point begins serving the public. New community and nontransient noncommunity groundwater entry points at which nitrate and nitrite are not detected at levels equal to or greater than 50% of the MCL, and all transient noncommunity entry points, shall begin initial annual monitoring during the first new calendar year after the entry point begins serving the public.
(C) Repeat monitoring for systems with nitrate or nitrite levels equal to or greater than 50% of the MCL.
(I) For entry points at which initial monitoring results or subsequent monitoring indicate nitrate or nitrite levels equal to or greater than 50% of the MCL, community and nontransient noncommunity water systems shall begin quarterly monitoring the quarter following detection at that level and continue quarterly monitoring for both nitrate and nitrite, unless reduced monitoring is granted in accordance with subclause (III).
(II) For entry points at which initial monitoring results or subsequent monitoring indicate nitrate or nitrite levels greater than the MCL, transient noncommunity systems shall begin quarterly monitoring the quarter following detection at that level and continue quarterly monitoring for both nitrate and nitrite, unless reduced monitoring is granted in accordance with subclause (IV).
(III) After four consecutive quarterly samples at an entry point for a community or nontransient noncommunity system indicate nitrate and nitrite levels in each sample are less than 50% of the MCLs, the required compliance monitoring is reduced to one sample per year at the entry point. Annual monitoring shall be conducted during the calendar quarter in which the consecutive quarterly monitoring indicated that the highest levels of contamination were present, unless the Department determines that a different monitoring quarter should be used in accordance with paragraph (10).
(IV) After four consecutive quarterly samples at an entry point for a transient noncommunity system indicate nitrate and nitrite levels in each sample are less than the MCLs, the required compliance monitoring is reduced to one sample per year at the entry point. Annual monitoring shall be conducted during the calendar quarter in which the consecutive quarterly monitoring indicated that the highest levels of contamination were present, unless the Department determines that a different monitoring quarter should be used in accordance with paragraph (10).
(V) For nitrate or nitrite sample results in excess of the MCLs, the water supplier shall take a confirmation sample within 24 hours of having received the original sample result. Noncommunity water systems for which an alternate nitrate level has been approved by the Department in accordance with 40 CFR 141.11(d) are not required to collect a confirmation sample if only the nitrate MCL is exceeded and nitrate is not in excess of the alternate nitrate level. If the alternate nitrate level is exceeded, the water supplier shall collect a confirmation sample within 24 hours after being advised by the certified laboratory performing the analysis that the compliance sample exceeded 20 mg/l for nitrate. Confirmation monitoring shall be completed by the deadline for compliance monitoring. Quarterly performance monitoring is required for nitrate and nitrite at entry points where treatment has been installed to remove nitrate or nitrite.
(D) Repeat monitoring for systems with nitrate and nitrite levels less than 50% of the MCLs. For entry points at which initial monitoring results indicate nitrate and nitrite levels in each sample are less than 50% of the MCLs, nitrate and nitrite monitoring shall be repeated annually during the calendar quarter in which the water supplier anticipates the highest levels of contamination, unless the Department determines that a different monitoring quarter should be used in accordance with paragraph (10).
(iii) Monitoring requirements for antimony, arsenic, barium, beryllium, cadmium, cyanide, chromium, fluoride, mercury, nickel, selenium and thallium.
(A) Initial monitoring schedule. Community water systems and nontransient noncommunity water systems shall monitor each surface water entry point annually beginning during the year beginning January 1, 1993, and shall monitor each groundwater entry point once every 3 years beginning during the year beginning January 1, 1994.
(B) Monitoring of new entry points. New groundwater entry points which begin operation after December 31, 1994, shall begin initial monitoring in accordance with the schedule in clause (A)--that is, 1997, and so forth. New surface water entry points shall begin initial annual monitoring during the first new calendar year after the entry point begins serving the public.
(C) Repeat monitoring for entry points at which an IOC MCL is exceeded.
(I) For entry points at which initial monitoring results or subsequent monitoring indicates an IOC level in excess of the MCL, monitoring shall be repeated quarterly beginning the quarter following detection at that level for each IOC in excess of an MCL, until reduced monitoring is granted in accordance with subclause (II).
(II) After analyses of four consecutive quarterly samples at an entry point where treatment has not been installed to comply with an IOC MCL indicate that contaminant levels are less than the MCLs, the required monitoring for each IOC less than the MCL is reduced to the frequencies stated in clause (A). This reduced monitoring option does not apply to entry points at which treatment has been installed for IOC removal. Compliance monitoring for IOCs for which treatment has been installed to comply with an MCL shall be conducted at least annually, and performance monitoring shall be conducted quarterly.
(III) A confirmation sample shall be collected and analyzed for each IOC listed under 40 CFR 141.11(b) or 141.62(b) which is detected at a level in excess of its MCL during annual or less frequent compliance monitoring. The confirmation sample shall be collected within 2 weeks of notification by the certified laboratory performing the analysis that an MCL has been exceeded. The average of the results of the original and the confirmation samples will be used to determine compliance. Confirmation monitoring shall be completed by the deadline specified for IOC compliance monitoring.
(D) Waivers for IOC monitoring. Except when treatment has been installed to remove the IOC, after three consecutive rounds of quarterly, annual or triennial monitoring indicate the contaminant level for an IOC is below the MCL in all samples at an entry point, routine monitoring for the remainder of the compliance cycle for that IOC is waived and the required monitoring for the IOC is reduced to one sample per 9-year compliance cycle at that entry point. Reduced monitoring shall be conducted during the first monitoring period of the next monitoring cycle. A waiver is effective for one compliance cycle and may be renewed in each subsequent compliance cycle.
(E) Operational monitoring for fluoride. Public water suppliers who fluoridate shall conduct operational monitoring for fluoride daily.
(8) Monitoring requirements for public water systems that obtain finished water from another public water system.
(i) Consecutive water suppliers shall monitor for compliance with the MCL for microbiological contaminants at the frequency established by the EPA and incorporated by reference into this chapter.
(ii) Community consecutive water suppliers shall:
(A) Monitor for compliance with the MCL for total trihalomethanes (TTHMs) at the frequency established by the EPA and incorporated by reference into this chapter if the system does one of the following:
(I) Serves more than 10,000 persons.
(II) Obtains finished water from another public water system serving more than 10,000 persons.
(B) Monitor the distribution system for compliance with the MCL for asbestos at the frequency indicated in paragraph (7)(i), when the Department determines that the system's distribution system contains asbestos cement pipe and optimum corrosion control measures have not been implemented.
(iii) Consecutive water suppliers are exempt from conducting monitoring for the MCLs for VOCs, SOCs and IOCs if the public water system from which the finished water is obtained complies with paragraphs (5)--(7), except that asbestos monitoring is required in accordance with subparagraph (ii)(B).
(iv) For a public water system which is not a consecutive water system, the exemption in subparagraph (iii) applies to entry points which obtain finished water from another public water system.
(v) A public water supplier that obtains finished water from another permitted public water system using surface water sources shall, beginning May 16, 1992, measure the residual disinfectant concentration at representative points in the distribution system at least as frequently as the frequency required for total coliform sampling for compliance with the MCL for microbiological contaminants.
(9) Monitoring requirements for POE devices. A public water supplier using a POE device shall, in addition to the monitoring requirements specified in paragraphs (1)--(8), conduct monitoring on the devices installed. As a minimum, the monitoring shall include the MCLs for which the POE device is intended to treat and monthly microbiological monitoring. The Department may allow the water supplier to reduce the frequency of microbiological monitoring based upon historical performance. Except for microbiological contaminants, monitoring shall be performed quarterly on 25% of the installed POE devices with the locations rotated so that each device is monitored at least once annually, unless increased monitoring is required by the Department under § 109.302.
(10) Additional monitoring. The Department may by written notice require a public water supplier to conduct monitoring for compliance with MCLs during a specific portion of a monitoring period, if necessary to ensure compliance with the monitoring or reporting requirements in this chapter.
(11) Monitoring requirements for entry points that do not provide water continuously. Entry points from which water is not provided during every quarter of the year shall monitor in accordance with paragraphs (5)--(7), except that monitoring is not required during a quarter when water is not provided to the public, unless special monitoring is required by the Department under § 109.302.
Subchapter G. SYSTEM MANAGEMENT RESPONSIBILITIES § 109.701. Reporting and recordkeeping.
(a) Reporting requirements for public water systems. Public water systems shall comply with the following requirements:
(1) General reporting requirements. Unless a shorter period is specified in this section, the water supplier shall assure that the results of test measurements or analyses required by this chapter are reported to the Department within either the first 10 days following the month in which the result is received or the first 10 days following the end of the required monitoring period as stipulated by the Department, whichever is shorter. The test results shall include the following at a minimum:
(i) The name, address and public water system identification number (PWSID) of the public water system from which the sample was taken.
(ii) The name, address and identification number of the laboratory performing the analysis unless the analysis is not required to be performed by a certified laboratory.
(iii) The results of analytical methods, including negative results.
(iv) Contaminants.
(v) Analytical methods used.
(vi) The date of sample.
(vii) The date of analysis.
(viii) Sample location.
(2) Monthly reporting requirements for performance monitoring.
(i) The test results of performance monitoring required under § 109.301(1) (relating to general monitoring requirements) for public water suppliers providing filtration and disinfection of surface water sources shall include the following at a minimum:
(A) For turbidity performance monitoring:
(I) The number of days of filtration operation.
(II) The number of measurements taken each month.
(III) The number of measurements that equal or exceed .5 NTU for conventional, direct or other filtration technologies, or 1.0 NTU for slow sand or diatomaceous earth filtration technologies.
(IV) The date, time and values of measurements exceeding 2.0 NTU.
(B) For performance monitoring of the residual disinfectant concentration of the water being supplied to the distribution system:
(I) The date, time and lowest value each day.
(II) The date, duration and number of periods each day when the concentration is less than .2 mg/l for more than 4 hours.
(C) For performance monitoring of the residual disinfectant concentration at representative points in the distribution system report the following:
(I) The number of monthly routine samples required.
(II) The number of monthly routine samples collected and analyzed.
(III) The number of samples in which the residual disinfectant concentration was less than 0.02 mg/l.
(IV) For samples in which the residual disinfectant concentration was less than 0.02 mg/l: the date, time and value of each sample.
(ii) The test results of performance monitoring required under § 109.301(2) for public water suppliers using unfiltered surface water sources shall include the following, at a minimum:
(A) For turbidity performance monitoring:
(I) The date, time and value of each sample that exceeds 1.0 NTU.
(II) The date, time and highest turbidity value, if the turbidity does not exceed 1.0 NTU in a sample.
(B) For performance monitoring of the residual disinfectant concentration of the water being supplied to the distribution system:
(I) The date, time and lowest value each day the concentration is less than the residual disinfectant concentration required under § 109.202(c)(1)(iii) (relating to State MCLs and treatment technique requirements).
(II) If the concentration does not fall below that required under § 109.202(c)(1)(iii) during the month, report the date, time and lowest value measured that month.
(C) For performance monitoring of the residual disinfectant concentration at representative points in the distribution system, report the following:
(I) The number of monthly routine samples required.
(II) The number of monthly routine samples collected and analyzed.
(III) The number of samples in which the residual disinfectant concentration was less than 0.02 mg/l.
(IV) For samples in which the residual disinfectant concentration was less than 0.02 mg/l: the date, time and value of each sample.
(D) For performance monitoring of the fecal coliform or total coliform density determinations on samples of the source water immediately prior to disinfection: the date, time and value of each sample.
(iii) The test results from performance monitoring required under § 109.301(7)(v) of the residual disinfectant concentration of the water in the distribution system shall include the date, time and value of each sample.
(iv) The test results of heterotrophic plate count measurements taken under § 109.710(b) (relating to disinfectant residual in the distribution system) shall include the date, time and value of each sample.
(3) Compliance report. The water supplier shall report to the Department within 48 hours failure to comply with Subchapter C (relating to monitoring requirements), except that emergency notification shall be made under § 109.402 (relating to emergency public notification).
(4) Notice. The water supplier shall, within 10 days of completion of each public notification required under Subchapter D (relating to public notification), submit to the Department a representative copy of each type of notice and a description of the publication, distribution, posting or other means undertaken to make the notice available.
(5) Siting plan. The water supplier shall submit to the Department a written sample siting plan for routine coliform sampling as required by § 109.303(a)(2) within 30 days of receipt of the Department's request for this information.
(i) A sample siting plan shall include at a minimum the following:
(A) A list of available sample site locations in the distribution system to be used for routine monitoring purposes, including the first service connection (or Department approved equivalent) and dead ends.
(B) The name of the company or individual collecting the samples.
(C) A time period by which available sites representative of the distribution system are to be sampled during each monitoring period.
(ii) The Department's approval of a sample siting plan will be based upon the following:
(A) The population served by the system.
(B) The accessibility of sample sites.
(C) The past monitoring history for the system.
(D) The completeness of the sample siting plan which includes the information specified in subparagraph (i) and other information relating to the criteria in this subparagraph necessary for evaluation of the sample siting plan.
(iii) A water supplier shall revise and resubmit its sample siting plan within 30 days of notification by the Department of a sample siting plan which fails to meet the criteria in subparagraphs (i) and (ii).
(iv) The water supplier shall notify the Department of subsequent revisions to an approved coliform sample siting plan for approval as they occur. Revisions to an approved coliform sample siting plan shall be submitted in written form to the Department within 30 days of notifying the Department of the revisions.
(6) Records. Upon request by the Department, the water supplier shall submit copies of records required to be maintained under this subchapter.
(7) Form. Reports required by this chapter shall be submitted in a manner or form acceptable to the Department.
(b) Reporting requirements for community water systems. In addition to the reporting requirements for a public water system, a community water supplier shall comply with the following requirements:
(1) The water supplier shall prepare a monthly operational report on forms provided by the Department or in a form acceptable to the Department. The report shall be maintained on file by the operator for at least 2 years and submitted upon request of the Department. The report shall include at least the following:
(i) The water produced daily.
(ii) The chemical added daily.
(iii) The physical and chemical determinations taken daily.
(iv) Water-level monitoring data for supply and any associated monitoring wells.
(v) The maintenance performed.
(vi) Operational problems.
(2) The water supplier shall submit by March 31 an annual water supply report for the prior calendar year on forms provided by the Department or in a form acceptable to the Department. This report shall include information relating to water use, connections, distribution system and storage.
(3) The water supplier shall keep a record of complaints received from consumers related to this act or this chapter on forms provided by the Department or in a form acceptable to the Department. Water suppliers complying with the Pennsylvania Public Utility Commission (PUC) complaint recordkeeping requirements under 52 Pa. Code § 65.3 (relating to complaints) shall be in compliance with this subsection if the complaints related to the act or this chapter are cross referenced within the PUC required records in a manner to make them readily available. The records shall be maintained on file by the operator for at least 3 years and submitted upon request of the Department.
(c) Reporting requirements for nontransient noncommunity water systems. In addition to complying with the reporting requirements for public water systems under subsection (a), a nontransient noncommunity water system shall comply with subsection (b)(1) except that records of water produced daily are not required.
(d) Record maintenance. The public water supplier shall retain on the premises of the public water system or at a convenient location near the premises the following:
(1) Records of bacteriological analyses which shall be kept for at least 5 years, and records of chemical analyses which shall be kept for at least 12 years. Actual laboratory reports may be kept, or data may be transferred to tabular summaries, if the following information is included:
(i) The date, place and time of sampling, and the name of the person who collected the sample.
(ii) Identification of the sample as to whether it was a routine distribution system sample, check sample, raw or finished water sample or other special purpose sample.
(iii) The date of analysis.
(iv) The laboratory, certification number and person responsible for performing the analysis.
(v) The analytical technique and methods used.
(vi) The results of the analysis.
(2) Records of performance monitoring required under § 109.301 which shall be kept for at least 3 years. At a minimum, these records shall contain the reporting requirements under subsection (a).
(3) Records of action taken by the public water supplier to correct violations of MCLs or treatment technique requirements, which shall be kept for at least 3 years after the last action taken with respect to the particular violation involved.
(4) Copies of written reports or communications relating to sanitary surveys conducted by a water supplier or his agent, which shall be kept for at least 12 years.
(5) Records concerning a variance or exemption granted to the system which shall be kept at least 5 years following the expiration of the variance or exemption.
(6) Plans, specifications and permits for water system facilities which shall be kept for the life of the facility.
(7) Records concerning the use of acrylamide and epichlorohydrin shall be kept for at least 12 years. These records shall include verification that the chemicals used were certified for conformance with ANSI/NSF Standard 60 in accordance with § 109.606 (relating to chemicals, materials and equipment) and that the combination--or product--of dose and monomer level did not exceed the following:
(i) Acrylamide = 0.05% dosed at 1 ppm (or equivalent).
(ii) Epichlorohydrin = 0.01% dosed at 20 ppm (or equivalent).
Subchapter J. BOTTLED WATER AND VENDED WATER SYSTEMS, RETAIL WATER FACILITIES AND BULK WATER HAULING SYSTEMS § 109.1003. Monitoring requirements.
(a) General monitoring requirements. Bottled water and vended water systems, retail water facilities and bulk water hauling systems shall monitor for compliance with the MCLs in accordance with § 109.301 (relating to general monitoring requirements) and shall comply with § 109.302 (relating to special monitoring requirements). The monitoring requirements shall be applied as follows, except that systems which have installed treatment to comply with a primary MCL shall conduct quarterly operational monitoring for the contaminant which the facility is designed to remove:
(1) Bottled water systems, retail water facilities and bulk water hauling systems, for each entry point shall:
(i) Monitor for microbiological contaminants weekly.
(ii) Monitor for turbidity every 4 hours or continuously each day a surface water source is in use.
(iii) Monitor for compliance with the MCLs for VOCs in accordance with § 109.301(5) beginning during the quarter that begins January 1, 1995, except that:
(A) Systems that obtain finished water from another permitted public water system are exempt from conducting monitoring for the VOCs if the public water system supplying the finished water performs the required monitoring at least annually and a copy of the analytical reports are received by the Department.
(B) For systems in existence prior to January 1, 1995, that obtain raw water from only protected groundwater sources, initial monitoring for compliance with the MCLs for VOCs established by the EPA under 40 CFR 141.61(a) (relating to MCLs for organic contaminants) on January 30, 1991, and July 17, 1992, will be reduced to one sample for entry points or systems which meet the following conditions:
(I) The VOC monitoring required by the Department between January 1, 1988, and December 31, 1994, has been conducted and no VOCs were detected.
(II) The first quarter of VOC monitoring required by this subparagraph has been conducted during the first quarter of 1995 with no detection of a VOC.
(C) Initial monitoring of new entry points associated with new sources which are permitted in accordance with § 109.1005 (relating to permit requirements) to begin operation after December 31, 1994, shall be conducted as follows:
(I) Entry points at which a VOC is detected during new source monitoring shall be monitored quarterly beginning the first quarter the entry points begin serving the public. Quarterly monitoring shall continue until reduced monitoring is granted in accordance with clause (D)(I).
(II) Entry points at which no VOC is detected during new source monitoring shall begin initial quarterly monitoring during the first calendar quarter of the year after the entry point begins serving the public.
(D) Repeat monitoring for entry points shall be conducted as follows:
(I) For an entry point at which a VOC is detected during initial monitoring or where a VOC is detected anytime at a level in excess of its MCL, compliance monitoring shall be repeated quarterly for the VOCs for which the EPA has established MCLs under 40 CFR 141.61(a), except for vinyl chloride as provided in § 109.301(5)(i). After analyses of four consecutive quarterly samples at an entry point, including initial quarterly monitoring samples, demonstrate that the VOC levels in each quarterly sample are less than the MCLs, the required compliance monitoring is reduced to one sample per year at that entry point for all 21 VOCs, except for vinyl chloride as provided in § 109.301(5)(i).
(II) For a groundwater or surface water entry point at which VOCs are not detected during the initial and subsequent repeat monitoring, repeat monitoring shall be one sample per year from that entry point.
(iv) Conduct initial and repeat monitoring for compliance with the MCLs for SOCs--pesticides and PCBs--in accordance with § 109.301(6) for four consecutive quarters beginning during the quarter that begins January 1, 1995, except that:
(A) Systems that obtain finished water from another permitted public water system are exempt from conducting compliance monitoring for the SOCs if one of the following applies:
(I) The public water system supplying the finished water performs the required monitoring annually and a copy of the analytical results are received by the Department.
(II) The public water system supplying the water has been granted a waiver from conducting the initial or repeat compliance monitoring, or both, for one or more SOCs under § 109.301(6)(v). This exemption from conducting compliance monitoring applies only to SOCs indicated in the waiver.
(B) Systems which are granted an initial monitoring waiver in accordance with § 109.301(6)(v) are exempt from conducting compliance monitoring for the SOCs indicated in the waiver.
(C) Initial monitoring of new entry points associated with new sources which are permitted in accordance with § 109.1005 to begin operation after December 31, 1994, shall be conducted as follows:
(I) Entry points at which an SOC is detected during new source monitoring shall be monitored quarterly beginning the first quarter the entry points begin serving the public. Quarterly monitoring shall continue until reduced monitoring is granted in accordance with clause (D)(I).
(II) Entry points at which no SOC is detected during new source monitoring and which begin operation before April 1, 1995, shall conduct initial quarterly monitoring beginning during the quarter beginning January 1, 1995.
(III) Entry points at which no SOC is detected during new source monitoring and which begin operation after March 31, 1995, shall conduct initial quarterly monitoring beginning during the first calendar quarter of the year after the entry point begins serving the public.
(D) Repeat monitoring for entry points shall be conducted as follows:
(I) For entry points at which an SOC is detected during initial monitoring or where an SOC is detected anytime in excess of its MCL, compliance monitoring shall be repeated quarterly for the detected SOC for which the EPA has an established MCL under 40 CFR 141.61(c). After analyses of four consecutive quarterly samples at an entry point, including initial quarterly monitoring samples, demonstrate that the SOC level in each quarterly sample is less than the MCL, the required compliance monitoring is reduced for each SOC below the MCL to one sample per year at that entry point.
(II) For a groundwater or surface water entry point at which SOCs are not detected during the initial and any subsequent repeat monitoring, repeat monitoring shall be one sample per year from that entry point.
(v) Beginning in 1995, monitor for the primary IOCs, including lead and copper annually, except that:
(A) Systems are granted a waiver from asbestos monitoring unless the Department determines that the system's finished water is vulnerable to asbestos contamination by means of an asbestos cement pipe or the system's source water is vulnerable to asbestos contamination.
(B) Systems that obtain finished water from another permitted public water system are exempt from conducting compliance monitoring for the IOCs, except lead, copper and asbestos if the supplying system has not optimized corrosion control, if the public water system supplying the finished water performs the required monitoring annually and a copy of the analytical results is received by the Department.
(C) Monitoring for compliance with the MCLs for nitrate and nitrite shall be conducted quarterly following a monitoring result which is equal to or greater than 50% of the MCL. After four consecutive quarterly samples, indicate nitrate and nitrite in each sample are less than 50% of the MCLs, required monitoring is reduced to one sample per year.
(vi) Conduct operational monitoring for fluoride at least once each day, if the system fluoridates its water.
(vii) Monitor for compliance with radiological MCLs once every 4 years.
(2) Vended water systems shall monitor in accordance with paragraph (1) except that vended water systems qualifying for permit by rule under § 109.1005(b) (relating to permit requirements), for each entry point shall:
(i) Monitor monthly for microbiological contaminants.
(ii) Monitor annually for total dissolved solids, lead and cadmium.
(iii) Conduct special monitoring as required by the Department.
(b) Special monitoring requirements for unregulated contaminants. Bottled water and vended water systems, retail water facilities and bulk water hauling systems, except vended water systems permitted by rule, shall monitor for the unregulated contaminants in accordance with the initial monitoring schedule for VOCs as prescribed in subsection (a).
(c) Sampling requirements.
(1) For bottled water and vended water systems, retail water facilities and bulk water hauling systems, samples taken to determine compliance with MCLs, monitoring requirements, including special monitoring requirements for unregulated contaminants, and treatment techniques shall be taken from each entry point.
(i) For bottled water systems, each entry point means each finished bottled water product. If multiple sources are used for a product and are not blended prior to bottling, the bottled water product for each source shall be considered a different product for monitoring purposes.
(ii) For bulk water hauling systems, retail water facilities and vended water systems, each entry point shall mean a point of delivery to the consumer from each carrier vehicle, machine or dispenser representative of each source.
(2) For the purpose of determining compliance with the monitoring and analytical requirements established under this subchapter, the Department will consider only those samples analyzed by a laboratory certified by the Department, except that measurements of turbidity, fluoridation operation, residual disinfection concentration, temperature and pH may be performed by a person meeting the requirements of § 109.1008(c) (relating to systems management responsibilities).
(3) Public water suppliers shall assure that samples for laboratory analysis are properly collected and preserved, are collected in proper containers, do not exceed maximum holding times between collection and analysis and are handled in accordance with guidelines governing quality control which may be established by the Department. A public water supplier who utilizes a certified laboratory for sample collection as well as analysis satisfies the requirements of this subsection.
(4) Compliance monitoring samples for VOCs, as required under subsection (a)(1)(iii), and for the unregulated contaminants as required under subsection (b), shall be collected by a person properly trained by a laboratory certifed by the Department to conduct VOC or vinyl chloride analysis.
(5) Compliance monitoring samples required under subsections (a)(1)(iii) and (b) may be composited in accordance with 40 CFR 141.24(g)(7) (relating to organic chemicals other than total trihalomethanes, sampling and analytical requirements) except:
(i) Samples from groundwater entry points may not be composited with samples from surface water entry points.
(ii) Samples from one type of bottled water product or vended water product may not be composited with samples from another type of bottled water product or vended water product.
(iii) Samples used in compositing shall be collected in duplicate.
(iv) If a VOC listed under 40 CFR 141.61(a) is detected at an entry point, samples from that entry point may not be composited for subsequent compliance or repeat monitoring requirements.
(v) Samples obtained from an entry point which contains water treated by a community water supplier or nontransient noncommunity water supplier to specifically meet an MCL for a VOC listed under 40 CFR 141.61(a) may not be composited with other entry point samples.
(d) Repeat monitoring for microbiological contaminants.
(1) If a sample collected in accordance with subsection (a)(1)(i) is found to be total coliform-positive:
(i) The bottled water system shall collect a set of 3 additional samples (check) from the same lot or batch of the type of product.
(ii) The vended water, retail water facility or bulk water hauling systems shall collect a set of four additional samples (check) from the same entry point (machine, point of delivery or carrier vehicle).
(2) Samples shall be collected for analysis within 24 hours of being notified of the total coliform-positive sample. The Department may extend this 24-hour collection limit to a maximum of 72 hours if the system adequately demonstrates a logistical problem outside the system's control in having the check samples analyzed within 30 hours of collection. A logistical problem outside the system's control may include a coliform-positive result received over a holiday or weekend in which the services of a Department certified laboratory are not available within the prescribed sample holding time.
(3) If a check sample is total coliform-positive, the system shall be deemed to have violated the MCL for total coliforms established under § 109.1002 (relating to MCLs or treatment techniques).
[Continued on next Web Page]
No part of the information on this site may be reproduced for profit or sold for profit.This material has been drawn directly from the official Pennsylvania Bulletin full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.