AIR QUALITY

PLAN APPROVAL AND OPERATING PERMIT APPLICATIONS

NEW SOURCES AND MODIFICATIONS

 The Department has developed an ''integrated'' plan approval, State Operating Permit and Title V Operating Permit program. This integrated approach is designed to make the permitting process more efficient for the Department, the regulated community and the public. This approach allows the owner or operator of a facility to complete and submit permitting documents relevant to its application one time, affords an opportunity for public input and provides for sequential issuance of the necessary permits.

 The Department received applications for Plan Approvals or Operating Permits from the following facilities.

 Copies of these applications, subsequently prepared draft permits, review summaries and other support materials are available for review in the regional office listed before the applications. Persons interested in reviewing the application files should contact the appropriate regional office to schedule appointments.

 Persons wishing to receive a copy of a proposed Plan Approval or Operating Permit shall indicate interests to the Department regional office within 30 days of the date of this notice and shall file protests or comments on a proposed Plan Approval or Operating Permit within 30 days of the Department providing a copy of the proposed documents to persons or within 30 days of its publication in the Pennsylvania Bulletin, whichever comes first.

 Interested persons may also request that hearings be held concerning a proposed Plan Approval or Operating Permit. A comment or protest filed with the Department regional office shall include a concise statement of the objections to the issuance of the Plan Approval or Operating Permit and relevant facts which serve as the basis for the objections. If the Department schedules a hearing, a notice will be published in the Pennsylvania Bulletin at least 30 days prior the date of the hearing.

 Persons with a disability who wish to comment and require an auxiliary aid, service or other accommodation to participate should contact the regional office listed before the application. TDD users may contact the Department through the Pennsylvania AT&T Relay Service at (800) 654-5984.

 Final Plan Approvals and Operating Permits will contain terms and conditions to ensure that the source is constructed and operating in compliance with applicable requirements in 25 Pa. Code Chapters 121—143, the Federal Clean Air Act (42 U.S.C.A. §§ 7401—7671q) and regulations adopted under the Federal Clean Air Act.

PLAN APPROVALS


Plan Approval Applications Received under the Air Pollution Control Act (35 P. S. §§ 4001—4015) and 25 Pa. Code Chapter 127, Subchapter B that may have special public interest. These applications are in review and no decision on disposition has been reached.

Northcentral Region: Air Quality Program, 208 West Third Street, Williamsport, PA 17701

Contact: Muhammad Q. Zaman, Environmental Program Manager—Telephone: 570-327-3648

57-00005B: Appalachia Midstream Services, LLC (PO Box 54382, Oklahoma City, OK 73154-1382) accepted for technical review proposal to construct and operate dehydration process at their company's Cherry Compressor Station facility in Cherry Township, Sullivan County.


Intent to Issue Plan Approvals and Intent to Issue or Amend Operating Permits under the Air Pollution Control Act and 25 Pa. Code Chapter 127, Subchapter B. These actions may include the administrative amendments of an associated operating permit.

Southeast Region: Air Quality Program, 2 East Main Street, Norristown, PA 19401

Contact: Sachin Shankar, New Source Review Chief—Telephone: 484-250-5920

46-0005AM: Merck, Sharp & Dohme, Corp. (770 Sunmeytown Pike, West Point, PA 19486-0004) for removal of a previously permitted air pollution control device (catalytic oxidizer, Source Number C161) in Upper Gwynedd Township, Montgomery County. The bypass of this control device is currently allowed in the Title V operating permit, under Alternative Operating Scenarios. The overall air emissions associated with the removal of this control device will decrease as the facility has committed to processing product with either zero or low VOCs in their batches. This project does not trigger applicability toward PADEP's NSR regulations or the federal PSD regulations. The plan approval will include monitoring, recordkeeping and reporting requirements designed to keep the facility operating within all applicable air quality requirements.

Southcentral Region: Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110

Contact: Thomas J. Hanlon, Facility Permitting Chief— Telephone: 717-705-4862 or William Weaver, Program Manager—Telephone: 717-705-4702.

06-05150A: Berks Hollow Energy Associates, LLC (400 Chesterfield Center, Suite 110, Chesterfield, MO 63017) for an electric generation plant to be located at 5662 Leesport Avenue in Ontelaunee Township, Berks County.

 In accordance with 25 Pa. Code §§ 127.44(a) and 127.45(a), the Department of Environmental Protection (DEP) has received an application, and intends to issue a Plan Approval to the abovementioned company for the abovementioned project.

 Plan Approval 06-05150A is for installation and startup of a combined-cycle natural gas fired electric generation station. The company shall be subject to and comply with 40 CFR 60 Subpart KKKK (Standards of Performance for Stationary Combustion Turbines), 40 CFR 60 Subpart IIII (Standards of Performance for Stationary Compression Ignition Internal Combustion Engines), 40 CFR 72 (Acid Rain Program), 40 CFR 97 (Clean Air Interstate Rule (CAIR)), 40 CFR 52 for Greenhouse Gases, Prevention of Significant Deterioration (PSD) of Air Quality regulations of 40 CFR 52.21, the Nonattainment New Source Review (NNSR) regulations of 25 Pa. Code §§ 127.201—127.218, and the Best Available Technology (BAT) requirements of 25 Pa. Code §§ 127.1 and 127.12. The Plan Approval will contain additional recordkeeping and operating restrictions designed to keep the facility operating within all applicable air quality requirements, including requirements to equip the combined-cycle units with a Selective Catalytic Reduction (SCR) unit and an oxidation catalyst for control of NOx and CO/VOC emissions, respectively, to meet BAT requirements. The proposed project has a potential-to-emit less than 267 tpy of NOx, 40 tpy of SO2, 430 tpy of CO, 104 tpy of PM-10, 100 tpy of PM-2.5, 189 tpy of VOC, 25 tpy of total HAP, 10 tpy of individual HAPs, 6 tpy of H2SO4 and 2.8 million tpy of CO2e.

 Pursuant to the Prevention of Significant Deterioration (PSD) provisions of 40 CFR 52.21 and 25 Pa. Code § 127.83, Berks Hollow Energy Associates, LLC (Berks Hollow) has performed an air quality analysis which utilizes dispersion modeling. The Berks Hollow air quality analysis satisfies the requirements of the PSD regulations and is consistent with the U.S. Environmental Protection Agency's (EPA) ''Guideline on Air Quality Models'' (40 CFR Part 51, Appendix W) and the EPA's air quality modeling policy and guidance. The Berks Hollow air quality analysis adequately demonstrates that Berks Hollow's proposed emissions will not cause or significantly contribute to air pollution in violation of the National Ambient Air Quality Standards for carbon monoxide (CO), nitrogen dioxide (NO2), and particulate matter less than or equal to 10 micrometers in diameter (PM-10), and the PSD increment standards for NO2 and PM-10. In addition, the analysis adequately demonstrates that Berks Hollow's proposed emissions, in conjunction with anticipated emissions due to general commercial, residential, industrial, and other growth associated with the Berks Hollow facility, will not impair visibility, soils, and vegetation. Furthermore, the analysis adequately demonstrates that Berks Hollow's proposed emissions will not adversely affect air quality related values, including visibility, in Federal Class I areas.

 In accordance with 40 CFR 52.21(l)(2), where an air quality model specified in the EPA's ''Guideline on Air Quality Models'' (40 CFR Part 51, Appendix W) is inappropriate, the model may be modified on a case-by-case basis. Written approval of the EPA Regional Administrator must be obtained for the use of a modified model. In addition, the use of a modified model must be subject to notice and opportunity for public comment under procedures developed in accordance with 40 CFR 52.21(q). The air quality analysis for NO2 for the proposed Berks Hollow facility utilizes the Plume Volume Molar Ratio Method (PVMRM), which is currently implemented as a non-regulatory default option within the EPA's recommended near-field dispersion model, the American Meteorological Society / Environmental Protection Agency Regulatory Model (AERMOD). In accordance with the recommendations under section 3.2 of the EPA's ''Guideline on Air Quality Models'' (40 CFR Part 51, Appendix W), the Department submitted a request to EPA Region III for approval of the use of the PVMRM within AERMOD for the Berks Hollow air quality analysis for NO2. EPA Region III approved the Department's request on February 22, 2013. Pursuant to 25 Pa. Code §§ 127.44 and 127.83, and 40 CFR 52.21(l)(2) and (q), notice is hereby given that the Department is expressly soliciting written comments on the use of the PVMRM in the Berks Hollow air quality analysis for NO2.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed plan approval, or may provide the Department with additional information to consider in its review, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed plan approval by the plan approval number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the plan approval.

 A 30-day comment period, from the date of publication of this notice in the Pennsylvania Bulletin, will exist for the submission of comments or protests, or for requests for a public hearing. A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted based on the comments received.

 Mr. Thomas Hanlon, Facilities Permitting Chief, may be contacted at 717-705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments, protests, or requests for a public hearing.

 Plan approvals issued to sources identified in 25 Pa. Code § 127.44(b)(1)—(4) or plan approvals issued to sources with limitations on the potential to emit may become part of the SIP, and will be submitted to EPA for review and approval.

22-05047C: Dura-Bond Pipe, LLC (2716 South Front Street, Steelton, PA 17113) for replacement of the two (2) baghouses controlling emissions from the outside diameter shot blast operations with a single baghouse and the replacement of the existing outside blowout baghouse with a baghouse removed from the shot blast operations in Steelton Borough, Dauphin County.

 In accordance with 25 Pa. Code §§ 127.44(a) and 127.45(a), the Department of Environmental Protection (DEP) has received and intends to issue a Plan Approval to the abovementioned company for the abovementioned project. This plan approval may be incorporated into the company's facility-wide permit via an administrative amendment at a later date.

 Plan Approval No. 22-05047C is for the replacement of the two (2) existing Wheelabrator baghouses, C201A & C201B, which control the outside diameter shot blast operations, Source Id 201. The baghouses will be replaced by a single 14,000 scfm custom made baghouse. Additionally, the existing Wheelabrator baghouse (C202) controlling the outside diameter blowout operations, Source Id 202, will be replaced with the 3,750 scfm Wheelabrator baghouse, C201A, being removed from the shot blast operations. The Plan Approval will contain testing, monitoring, recordkeeping & work practice standards designed to keep the facility operating within all applicable air quality requirements. Actual air emissions are not expected to change from this project since the throughput capacities for Sources 201 or 202 are changing. Actual particulate matter emissions from the two sources for the year 2011 have been reported to be 10.3 tons.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed plan approval, or may provide the Department with additional information to consider in its review, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period, from the date of publication of this notice in the Pennsylvania Bulletin, will exist for the submission of comments or protests, or for requests for a public hearing. A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted based on the comments received.

 Tom Hanlon, Facilities Permitting Chief, may be contacted at 717-705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments, protests, or requests for a public hearing.

Southwest Region: Air Quality Program, 400 Waterfront Drive, Pittsburgh, PA 15222-4745

Contact: M. Gorog & B. Hatch, Environmental Engineer Managers—Telephone: 412-442-4163/5226

32-00424A: Notice is hereby given that the Department of Environmental Protection intends to issue a Plan Approval (PA-32-00424A) to Western Allegheny Energy, LLC (301 Market Street, Kittanning, PA 16201) to authorize the construction and temporary operation of a coal preparation plant at their Brush Valley Mine located in Center Township, Indiana County.

 The facility's main sources and controls include Pit Conveyor, Clean Coal Conveyor, Radial Stackers, Double Deck Screen, ROM Stockpile, Oversize & Clean Coal Stockpiles, Two (2) Emergency diesel engines, Cummins 500DFEK rated at 732 bhp & Cummins 175DSHAB rated at 187 bhp, Front-end loader, and Truck loadout (100 trucks/day estimated). Roadways will be controlled by paving and water sprays whereas the fugitive emissions from the process will be controlled by water sprays and partial enclosures. Emissions from diesel engines will be controlled by limited hours of operation.

 This facility has the potential to emit the following type and quantity of air contaminants (on an annual basis): 76.1 tons of PM, 21.7 tons of PM10, 1.9 tons of PM2.5, 2.4 tons of NOx, and 1.5 tons of Carbon Monoxide. SOx, HAPs, and GHG being minimal are not included. The emission restriction, testing, monitoring, recordkeeping, reporting and work practice conditions of the Plan Approval have been derived from the applicable requirements of 40 CFR Part 60, 40 CFR Part 63, and 25 Pa. CodeChapters 123 and 127.

 Any person wishing to provide DEP with additional information that they believe should be considered prior to the issuance of this permit may submit the information to DEP at DEP, Southwest Regional Office, 400 Waterfront Drive, Pittsburgh, PA 15222. A 30-day comment period, from the date of this publication, will exist for the submission of comments. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed Plan Approval (Specify PA-32-00424A) and concise statements regarding the relevancy of the information in the proposed Plan Approval or objections to issuance of the Plan Approval.

 A public hearing may be held, if DEP, in its discretion, decides that such a hearing is warranted based on the information received. All persons submitting comments or requesting a hearing will be notified of the decision to hold a hearing by publication in the newspaper or by the Pennsylvania Bulletin, or by telephone, where DEP determines such notification by telephone is sufficient. Written comments or requests for a public hearing should be directed to Jesse Parihar, Air Quality Engineering Specialist, DEP, Southwest Regional Office, 400 Waterfront Drive, Pittsburgh, PA 15222, (412) 442-4030.

63-00979A: Liquidmetal Coatings, LLC (50 Technology Drive, California, PA 15423) for metal coating, engraving, and allied services to manufacturers at Liquidmetal Coatings in California Boro, Washington County. This is a minor facility Plan Approval application submittal.

Northwest Region: Air Quality Program, 230 Chestnut Street, Meadville, PA 16335-3481

Contact: Edward Orris, New Source Review Chief—Telephone: 814-332-6636

16-161A: Kelly IMG Energy, LLC (301 Oxford Valley Road, Yardley, PA 19067) for construction of a 6.2 MW natural gas-fired electric generating station at their proposed facility on Zanot Road, Toby Township, Clarion County.

 Notice is hereby given pursuant to 25 Pa. Code §§ 127.44(b) and 127.424(b), that the Pennsylvania Department of Environmental Protection (DEP) intends to issue Plan Approval 16-161A to Kelly IMG Energy, LLC for the construction of a 6.2 MW natural gas-fired electric generating station at their proposed facility on Zanot Road, Toby Township, Clarion County. The Plan Approval will subsequently be incorporated into the facility's Operating Permit through an administrative amendment in accordance with 25 Pa. Code § 127.450.

 Plan Approval No. 16-161A is for the construction of a natural gas-fired electric generating station, to consist of two (2) 4350 bhp natural gas fired generator engines and associated oxidation catalyst control devices. Based on the information provided by the applicant and DEP's own analysis, the proposed sources will emit a maximum of 42.02 tons of nitrogen oxides (NOx), 6.72 tons of carbon monoxide, 5.04 tons of volatile organic compounds (VOC), 2.44 tons of particulate matter less than 10 microns (PM-10), 0.14 ton of sulfur oxides (SOx), 1.68 tons of formaldehyde, and 1.76 tons of total hazardous air pollutants (HAP) per year.

 The proposed sources will be subject to 40 CFR 60, Subpart JJJJ (Standards of Performance for Stationary Spark Ignition Internal Combustion Engines), the applicable requirements of which will be contained in the Plan Approval. The Plan Approval will contain additional testing, monitoring, recordkeeping, and work practice requirements designed to keep the facility operating within all applicable air quality requirements.

 Copies of the application, DEP's analysis, and other documents used in the evaluation are available for public inspection between the hours of 8 a.m. and 4 p.m. weekdays at the address shown below. To make an appointment, contact Records Management at 814-332-6340.

 Anyone wishing to provide DEP with additional information they believe should be considered may submit the information to the address shown below. Comments must be received by the Department within 30 days of the last day of publication. Written comments should include the name, address, and telephone number of the person submitting comments, identification of the proposed Plan Approval; No. 16-161A and concise statement regarding the relevancy of the information or any objections to issuance of the Plan Approval.

 A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted on the comments received during the public comment period. All persons submitting comments or requesting a hearing will be notified of the decision to hold a hearing by publication in a local newspaper of general circulation or the Pennsylvania Bulletin or by telephone, where the Department determines such notification is sufficient. Written comments or requests for a public hearing should be directed to John Guth, Regional Air Quality Manager, Department of Environmental Protection, Northwest Regional Office, 230 Chestnut St., Meadville, PA 16335, 814-332-6940.

37-337A: Hickory Run Energy, LLC (NE intersection of McClelland and Edinburg Road, New Castle, PA 16102) Notice is hereby given in accordance with 25 Pa. Code §§ 127.44(b) and 127.424(b) that the Department of Environmental Protection (DEP) intends to issue a plan approval to Hickory Run Energy, LLC to construct a natural gas-fired combined-cycle electric generation facility in North Beaver Township, Lawrence County. This is a PSD application and this is a Title V facility. The address of Hickory Run Energy, LLC is 400 Chesterfield Center, Suite 110, Chesterfield, Missouri 63017. The public notice is required for sources required to obtain a Plan Approval in accordance with 25 Pa. Code § 127.44. This plan approval will, in accordance with 25 Pa. Code § 127.450 or § 127.505, be incorporated into a new Title V operating permit at a later date. The Department intends to issue a plan approval for this construction and has submitted the proposed plan approval to U.S. Environmental Protection Agency (EPA) for its review.

 In accordance with 25 Pa. Code § 127.44(e)(1), all the pertinent documents regarding HRE's application (applications, review memos, and draft approvals) are also available for review from 8:00 a.m. to 4:00 p.m. at the Meadville Regional DEP office (Air Quality) located at 230 Chestnut Street, Meadville, PA. Appointments for scheduling a review must be made by calling the DEP at (814) 332-6340.

 In accordance with 25 Pa. Code § 127.44(e)(2), a 30-day comment period, from the date of publication, will exist for the submission of comments. Any person(s) wishing to provide DEP with additional information, which they believe should be considered prior to the issuance of this permit, may submit the information to Regional Air Quality Program Manager, Pennsylvania Department of Environmental Protection, 230 Chestnut Street, Meadville, PA 16335-3494 and must contain the name, address and telephone number of the person submitting the comments, identification of the proposed plan approval [37-337A] and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 In accordance with 25 Pa. Code §§ 127.45 and 127.46, a person may oppose the proposed plan approval by filing a written protest with the Department's Northwest Region.

 Public Hearing:

 Notice is hereby given pursuant to 25 Pa. Code §§ 127.44(b), 127.45 and 127.48 that the Department of Environmental Protection (DEP) will hold a public hearing on Wednesday April 3, 2013, at North Beaver Township VFD in North Beaver Township (969 Mount Jackson Road, New Castle, PA). The hearing will start at 6:00 PM. The hearing will conclude after all testimony has been received, but no later than 9:00 PM.

 The hearing is to provide testimony with regards to Hickory Run Energy (HRE) plan approval application to construct a natural gas-fired combined-cycle electric generation facility that is designed to generate up to 900 MW nominal, using 2 combustion turbine generators with duct burners and 2 heat recovery steam generators that will provide steam to drive a single steam turbine generator. The Department intends to issue a plan approval for this construction and will be submitting the proposed plan approval to U.S. Environmental Protection Agency (EPA) for its review.

 During the hearing, in accordance with 25 Pa. Code §§ 127.48 and 127.49, the Department will accept and record testimony concerning HRE's application. Persons wishing to present testimony at the hearing should contact Community Relations Coordinator Gary Clark, at (814) 332-6615, at least one week in advance of the hearing to reserve a time to present testimony. Oral testimony during the hearing will be limited to a maximum of five minutes and three written copies of the oral testimony, together with exhibits are required. Organizations are encouraged to designate one witness to present testimony on behalf of the organization. Persons unable to attend the hearing may submit three copies of a written statement and exhibits within 10 days thereafter to the Department in care of Regional Air Quality Program Manager, Department of Environmental Protection, 230 Chestnut Street, Meadville, PA 16335. Written submittals must contain the name, address and telephone number of the person submitting the comments, identification of the proposed plan approval [37-337A] and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 Persons with a disability who wish to comment and require an auxiliary aid, service or other accommodations to do so should contact Gary Clark or the Pennsylvania AT&T relay service at 1-800-654-5984 (TDD) to discuss how the Department may accommodate your needs.

 The plan approval is for the construction of a natural gas-fired combined-cycle electric generation facility that is designed to generate up to 900 MW nominally, using 2 combustion turbine generators and 2 heat recovery steam generators that will provide steam to drive a single steam turbine generator. Other air emission sources at the facility include a natural gas-fired auxiliary boiler; a diesel engine-driven emergency generator; a diesel engine-driven firewater pump; a multi-cell evaporative cooling tower; and associated emission control system, tanks, and other balance of plant equipment. Control technology for each combined cycle unit (CCU) will be Dry Low NOx combustors & Selective Catalytic Reduction system for NOx control (Lowest Achievable Emission Rate (LAER), Best Available Control Technology (BACT) and Best Available Technology (BAT), good combustion practices (GCP) and oxidation catalyst for CO (BACT and BAT) & VOC control (LAER, BACT, and BAT), pipeline quality natural gas for SOx and sulfuric acid mist control (BACT and BAT), GCP & pipeline quality natural gas for PM, PM10 and PM2.5 control (BACT and BAT), and energy efficiency for greenhouse gas (GHG) control (BACT and BAT). Best available technology for other sources will be the control of emissions through inherent low-emitting designs, low sulfur fuels, or good operating practices.

 This construction will result in facility emissions of 4,163,948.3 tpy of CO2(e), 807.53 tpy of CO, 0.001 tpy of lead, 216.13 tpy of VOC, 56.70 tpy of SOx, 346.09 tpy of NOx, 134.41 tpy of PM2.5, 137.26 tpy of PM10, 143.98 tpy of PM, 8.57 tpy of H2SO4, 221.14 tpy of ammonia, 6.9 tpy of a single HAP, and 15.3 tpy of all HAPs combined. The application was reviewed in accordance with Prevention of Significant Deterioration (PSD) and Non-Attainment New Source Review (NSR) requirements. Facility is subject to State and Federal requirements, including 40 CFR 60 Subpart Dc, IIII, & KKKK; Acid Rain Regulations (40 CFR 72-78); Clean Air Interstate Rule (CAIR) (40 CFR 96 & 97); Compliance Assurance Monitoring (CAM) (40 CFR 64); Risk Management Program (40 CFR 68—if applicable due to storing a regulated chemical on-site) and Greenhouse Gas Tailoring Rule (GHG) (40 CFR 51 and 52). To comply with these requirements, the plan approval contains conditions relating to emission limitations, testing, monitoring, recordkeeping, reporting, work practices, and additional requirements. This Plan Approval will contain conditions, which will satisfy the requirements of 25 Pa. Code § 127.12b (pertaining to plan approval terms and conditions) and will demonstrate BAT for the source including, but are not limited to, the following:

 • Nothing in this plan approval shall relieve the owner or operator from complying with any local zoning ordinances.

 • Emission Reduction Credit (ERC) Requirements

 • The permittee shall secure NOx and VOC ERCs sufficient to offset NOx and VOC emissions from the facility at a 1.15 to 1 ratio. ERCs shall be properly generated and certified by the Department. Upon transfer, the permittee shall provide the Department with documentation clearly specifying the details of the ERC transaction. The facility NOx PTE is based on 1.01 tpy for the Auxiliary Boiler, 0.49 tpy for the Emergency Generator, 0.09 tpy for the Emergency Fire Pump, and the NOx PTE for the Combined Cycle Units. The facility VOC PTE is based on 0.14 tpy for the Auxiliary Boiler, 0.03 tpy for the Emergency Generator, 0.06 tpy for the Emergency Fire Pump, and the VOC PTE for the Combined Cycle Units. The NOx and VOC PTE for the GE 7FA is 296.06 tpy and 215.84 tpy resulting in a facility NOx and VOC PTE of 297.65 tpy and 216.07 tpy. The NOx and VOC PTE for the Siemens SGT6-5000F5 is 298.0 tpy and 169.72 tpy resulting in a facility NOx and VOC PTE of 299.59 tpy and 169.95 tpy. The NOx and VOC PTE for the Mitsubishi M501GAC is 248.52 tpy and 187.62 tpy resulting in a facility NOx and VOC PTE of 250.11 tpy and 187.85 tpy. The NOx and VOC PTE for the Siemens SGT6-8000H is 344.5 tpy and 186.88 tpy resulting in a facility NOx and VOC PTE of 346.09 tpy and 187.11 tpy. The permittee shall obtain the following NOx and VOC ERCs based on the facility NOx and VOC PTE times the offset of 1.15:

 • GE 7FA: NOx—342.3 tons and VOC—248.5 tons

 • Siemens SGT6-5000F5: NOx—344.6 tons and VOC 195.5 tons

 • Mitsubishi M501GAC: NOx—287.7 tons and VOC 216.1 tons

 • Siemens SGT6-8000H: NOx—398.1 tons and VOC 215.2 tons

 • CCU (Source 031 & 032)

 • The source is subject to 40 CFR 60 Subpart KKKK

 • The source is subject to 40 FR 96 CAIR

 • The source is subject to the Acid Rain Regulations

 • No person may permit the emission into the outdoor atmosphere of the following in a manner that exceeds the following:

 • Nitrogen Oxides (NOx): Normal operation with or without duct burner: 2.0 ppmvd at 15% oxygen

 • NOx: 172.25 tpy based on 12-month rolling totals for each CCU

 • Carbon Monoxide (CO): Normal operation with or without duct burner: 2.0 ppmvd at 15% oxygen

 • CO: 401.88 tpy based on 12-month rolling totals for each CCU

 • Volatile Organic Compounds (VOC): Normal operation with or without duct burner: 1.9 ppmvd at 15% oxygen for GE 7FA.05 and Siemens SGT6-5000F5/DLN or 1.5 ppmvd corrected to 15% O2 for Mitsubishi M501GAC and Siemens SGT6-8000H/DLN

 • VOC: 107.92 tpy based on 12-month rolling totals for each CCU

 • Sulfur Oxides (SOx): 28.26 tpy based on 12-month rolling totals for each CCU

 • Sulfuric Acid (H2SO4): 4.26 tpy based on 12-month rolling totals for each CCU

 • Particulate Matter (PM)/PM10/PM2.5—66.91 tpy based on 12-month rolling totals for each CCU

 • Ammonia Slip (NH3 Slip)—5 ppmv, on a dry basis corrected at 15% oxygen

 • The emission limitations for NOx, CO, and ammonia are 3-hour rolling averages calculated once per hour and verified by CEMS. The emission limitations for VOC, SOx, H2SO4, and PM/PM10/PM2.5 are based on the average of three stack test runs.

 • A person may not permit the emission into the outdoor atmosphere of visible air contaminants in such a manner that the opacity of the emission is either of the following:

 • Equal to or greater than 10% for a period or periods aggregating more than 3 minutes in any 1 hour.

 • Equal to or greater than 10% for a period or periods aggregating more than 6 minutes during startup and shutdown.

 • The facility shall perform an initial stack test for PM (filterable & condensable), PM10 (filterable & condensable), PM2.5 (filterable & condensable), NOx, SOx, CO, VOC, ammonia slip, sulfuric acid, and HAPs (Formaldehyde) in accordance with the provisions of Chapter 139 of the Rules and Regulations of the Department of Environmental Protection.

 • The facility shall perform subsequent stack test for PM (filterable & condensable), PM10 (filterable & condensable), PM2.5 (filterable & condensable), VOC, sulfuric acid, and HAPs (Formaldehyde) in accordance with the provisions of Chapter 139 of the Rules and Regulations of the Department of Environmental Protection every two years (22 to 26 months after the date of the previous test).

 • The following conditions are related to CAM:

 • The permittee shall use the approved process parameter(s) or indicator(s) to obtain data and monitor the emission control equipment performance. A departure from the specified indicator range over a specified averaging period shall be defined as an excursion.

 • Oxidation Catalyst

 • Catalyst Temperature: Thermocouple or equivalent—continuously defined as a reading at least once every 15-minutes averaged over a 3-hour period

 • The following conditions are related to CEMs:

 • The following continuous emission monitoring system[s] (CEMS[s]) must be installed, approved by the Department, operated and maintained in accordance with the requirements of 25 Pa. Code Chapter 139, Subchapter C (relating to requirements for source monitoring for stationary sources) and the 'Submittal and Approval', 'Record Keeping and Reporting', and 'Quality Assurance' requirements of Revision No. 8 of the Department's Continuous Source Monitoring Manual, 274-0300-001. Compliance with any subsequently issued revision to the Continuous Source Monitoring Manual will constitute compliance with this permit condition.

 • CEMS #1: CO (ppmvd)

 • CEMS #2: NOx (ppmvd)

 • CEMS #3: CO2 (lbs/MW-hr gross)

 • CEMS #4: Ammonia (ppmvd)

 • The facility shall monitor Gross Electrical Output (MW-hr) in order to comply with the CO2 emission standard.

 • The following conditions are related to GHG:

 • No person may permit the emission into the outdoor atmosphere of the following in a manner that exceeds the following:

 • CO2 emission rate of 1,000 # / MW-hr (gross) on a 12-operating month annual average basis

 • CO2(e) emission rate of 2,075,069 tpy based on a 12-month rolling total for each CCU

 • Facility shall implement a sulfur hexafluoride (SF6) leak detection program to minimize SF6 leaks as follows. Circuit breakers are to be state-of-the-art sealed enclosed-pressure circuit breakers equipped with low-pressure alarms that are triggered when 10% of the SF6 by weight has escaped. When alarms are triggered, the facility will take corrective action as soon as practicable to fix the circuit breaker units to a like-new state to prevent the emission of SF6 to the maximum extent practicable.

 • Auxiliary Boiler (Source 033):

 • The emissions shall not exceed the following:

 • PM/PM10/PM2.5: 0.005 #/mmbtu or 0.46 tpy based on a 12-month rolling total

 • NOx: 0.011 #/mmbtu or 1.01 tpy based on a 12-month rolling total

 • CO: 0.036 #/mmbtu or 3.31 tpy based on a 12-month rolling total

 • VOC: 0.0015 #/mmbtu or 0.14 tpy based on a 12-month rolling total

 • SOx: 0.0021 #/mmbtu or 0.19 tpy based on a 12-month rolling total

 • H2SO4: 0.00048 #/mmbtu or 0.04 tpy based on a 12-month rolling total

 • CO2(e): 13,696 tpy based on a 12-month rolling basis

 • Subject to 40 CFR 60 Subpart Dc

 • Emergency Generator (Source 101):

 • The emissions shall not exceed the following:

 • PM/PM10/PM2.5: 0.33 #/hr or 0.02 tpy based on a 12-month rolling total

 • NOx: 9.89 #/hr or 0.49 tpy based on a 12-month rolling total

 • CO: 5.79 #/hr or 0.29 tpy based on a 12-month rolling total

 • VOC: 0.7 #/hr or 0.03 tpy based on a 12-month rolling total

 • SOx: 0.01 #/hr or 0.0007 tpy based on a 12-month rolling total

 • H2SO4: 0.0028 #/hr or 0.00014 tpy based on a 12-month rolling total

 • CO2(e): 80.5 tpy based on a 12-month rolling basis

 • Subject to 40 CFR 60 Subpart IIII

 • The annual operation during testing shall not exceed 100 hours per year.

 • The duration of each test shall not exceed 30 minutes.

 • The emergency generator and the emergency firewater pump shall not be tested simultaneously (within the same hour).

 • The emergency generator and the emergency firewater pump shall not be tested during (within the same hour as) startup or shutdown of the combustion turbines.

 • Emergency Fire Water Pump (Source 102):

 • The emissions shall not exceed the following:

 • PM/PM10/PM2.5: 0.15 #/hr or 0.01 tpy based on a 12-month rolling total

 • NOx: 1.86 #/hr or 0.09 tpy based on a 12-month rolling total

 • CO: 2.58 #/hr or 0.13 tpy based on a 12-month rolling total

 • VOC: 1.11 #/hr or 0.06 tpy based on a 12-month rolling total

 • SOx: 0.0055 #/hr or 0.00027 tpy based on a 12-month rolling total

 •  H2SO4: 0.0012 #/hr or 0.00006 tpy based on a 12-month rolling total

 • CO2(e): 33.8 tpy based on a 12-month rolling basis

 • Subject to 40 CFR 60 Subpart IIII

 • The annual operation during testing shall not exceed 100 hours per year.

 • The duration of each test shall not exceed 30 minutes.

 • The emergency generator and the emergency firewater pump shall not be tested simultaneously (within the same hour).

 • The emergency generator and the emergency firewater pump shall not be tested during (within the same hour as) startup or shutdown of the combustion turbines.

 • Cooling Water Tower (Source 103):

 • The PM/PM10/2.5 emissions shall not exceed 2.19/0.66/0.0039 #/hr.

 • The PM/PM10/PM2.5 emissions shall not exceed 9.59/2.87/0.017 tpy based on a 12-month rolling total.

 • The total dissolved solids (TDS) of the cooling tower water shall not exceed 5,000 ppmw.

 • The permittee shall, at a minimum of once per quarter, sample and analyze the cooling tower water for total dissolved solids (TDS) at a point which is representative of the water being evaporated to the atmosphere.

 • Fuel Storage Tanks (Source 104):

 • The company shall keep a record of the vapor pressure of the contents of the tanks unless the tank is equipped with pressure relief valves that meet the requirements in 25 Pa. Code § 129.57.

 • The company shall not store any liquid containing volatile organic compounds with vapor pressure greater than 1.5 psia (10.5 kilopascals) under actual storage conditions unless the tank is equipped with pressure relief valves which are maintained in good operating condition and which are set to release at no less than 0.7 psig (4.8 kilopascals) of pressure or 0.3 psig (2.1 kilopascals) of vacuum or the highest possible pressure and vacuum in accordance with state or local fire codes or the National Fire Prevention Association guidelines or other national consensus standards acceptable to the Department.

 Dispersion modeling was conducted for the proposed HRE facility with representative emission source data, terrain data, and meteorological data. The impacts of the emissions of carbon monoxide, nitrogen dioxide, particulate matter less than 10 micrometers, and sulfur dioxide from the proposed facility are estimated by modeling to be less than the significant impact levels established by the U.S. EPA; therefore, it is estimated by modeling that these emissions from the proposed facility will not cause or significantly contribute to air pollution in violation of the National Ambient Air Quality Standards or PSD increment standards. Modeling also demonstrated that emissions from the proposed facility of particulate matter less than 2.5 microns (PM2.5) in conjunction with existing ambient concentrations, do not cause or contribute to a violation of either the national ambient air quality standards or the PSD increment for PM2.5.

 The degree of PSD air quality increment consumption expected to result from operation of the HRES is as follows, based on the dispersion modeling analysis for the facility (all values given in micrograms per cubic meter):

 • NO2/NOx (annual average): 0.80 vs. standard of 25

 • PM2.5 (annual average): 0.04 vs. standard of 4

 • PM2.5 (24-hour average): 0.63 vs. standard of 9

 • PM10 (annual average): 0.53 vs. standard of 17

 • PM10 (24-hour average): 2.26 vs. standard of 30

 • SO2 (3-hour average): 0.91 vs. standard of 512

 • SO2 (24-hour average): 0.26 vs. standard of 91

 • SO2 (annual average): 0.018 vs. standard of 20

 This notice was also published in the New Castle News on March 2, March 4 and March 5, 2013.

Department of Public Health, Air Management Services: 321 University Avenue, Philadelphia, PA 19104

Contact: Edward Wiener, Chief—Telephone: 215-685-9426

OPERATING PERMITS


Intent to Issue Title V Operating Permits under the Air Pollution Control Act and 25 Pa. Code Chapter 127, Subchapter G.

Northeast Region: Air Quality Program, 2 Public Square, Wilkes-Barre, PA 18711-0790

Contact: Ray Kempa, New Source Review Chief—Telephone: 570-826-2507

54-00041: Silberline Manufacturing Co., Inc. (130 Lincoln Drive, P. O. Box B, Tamaqua, PA 18252) for operation of an aluminum pigment manufacturing and boilers operation in Rush Township, Schuylkill County. This action is a renewal of the Title V Operating Permit issued in 2005. These sources have the potential to emit major quantities of regulated pollutants (VOC) above Title V emission thresholds. The proposed Title V Operating Permit contains applicable requirements for emissions limitations, monitoring, record keeping, reporting, and work practice standards used to maintain facility compliance with Federal and State air pollution regulations.

Southcentral Region: Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110

Contact: Thomas J. Hanlon, Facility Permitting Chief—Telephone: 717-705-4862 or William Weaver, Program Manager—Telephone: 717-705-4702.

38-05019: PPL Ironwood LLC (305 Prescott Road, Lebanon, PA 17042) for their electric generating facility in South Lebanon Township, LebanonCounty.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue aTitle V Air Quality Operating Permit for the abovementioned facility.

 The subject facility has actual emissions of, based on 2011 data, approximately 212 tpy of NOx, 40 tpy of CO, 11 tpy of SOx, 49 tpy of PM10, 12 tpy of VOC and 7 tpy of HAPs. The Operating Permit will include emission limits and work practice standards along with monitoring, recordkeeping and reporting requirements to ensure the facility complies with the applicable air quality regulations. Among other items, the conditions include provisions derived from 40 CFR Part 60, Subpart GG—Standards of Performance for Stationary Gas Turbines.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office, at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed plan approval, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period, from the date of publication of this notice in the Pennsylvania Bulletin, will exist for the submission of comments or protests.

 Mr. Thomas Hanlon, Facilities Permitting Chief, may be contacted at 717-705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

67-05005: PPL Brunner Island, LLC (2 North 9th Street, Allentown, PA 18101) for their Brunner Island Steam Electric Station in East Manchester Township, York County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue a renewal of a Title V Air Quality Operating Permit for the abovementioned facility.

 The subject facility had the following actual air emissions in 2011: 17,657 tons SOx; 16,892 tons NOx; 1,419 tons PM10; 617 tons PM2.5; 839 tons CO; 2 tons VOC; 60 tons HCl; 15 tons HF; 2 tons Selenium; 1 ton Manganese; 1 ton Nickel; 80 tons total HAPs; 10,095,403 tons CO2; and 10,095,403 tons CO2e. The Operating Permit will include emission limits and work practice standards along with testing, monitoring, record keeping and reporting requirements to ensure the facility complies with all applicable air quality regulations. Unit Nos. 1, 2 and 3 (Source IDs 031A, 032 and 033A, respectively) are subject to the following requirements: 40 CFR Part 63, Subpart UUUUU—National Emission Standards for Hazardous Air Pollutants: Coal- and Oil-Fired Electric Utility Steam Generating Units; the NOx Budget Trading Program of 25 Pa. Code Chapter 145, Subchapter A; the Title IV Acid Rain Provisions of the Clean Air Act Amendments of 1990, as well as 25 Pa. Code § 127.531; the Clean Air Interstate Rule (CAIR) requirements of 25 Pa. Code Chapter 145, Subchapter D, and 40 CFR Part 97; the Compliance Assurance Monitoring (CAM) requirements of 40 CFR Part 64; and the continuous emission monitoring systems (CEMS) requirements of 25 Pa. Code § 139.101 and 40 CFR Part 75. The two emergency quench pump engines (Source IDs 037 and 038) are subject to the requirements of 40 CFR Part 60, Subpart IIII—Standards of Performance for Stationary Compression Ignition Internal Combustion Engines and 40 CFR Part 63, Subpart ZZZZ—National Emission Standards for Hazardous Air Pollutants for Stationary Reciprocating Internal Combustion Engines.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed operating permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the operating permit.

 A 30-day comment period from the date of publication of this notice in the Pennsylvania Bulletin will exist for the submission of comments or protests.

 William R. Weaver, Air Quality Program Manager, may be contacted at 717-705-4702, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

Northcentral Region: Air Quality Program, 208 West Third Street, Williamsport, PA 17701

Contact: Muhammad Zaman, Environmental Program Manager—Telephone: 570-327-3648

55-00005: Wood-Mode, Inc. (1 2nd St, PO Box 250, Kreamer, PA 17833) to issue a renewal Title V operating permit for their facility located in Middlecreek Township, Snyder County. The facility is currently operating under Title V Operating Permit 55-00005. The facility's main sources include three boilers, various woodworking operations, and surface coating of wood products. The facility has potential emissions of 128.4 tons per year of carbon monoxide, 61.4 tons per year of nitrogen oxides, 4.8 tons per year of sulfur oxides, 960.9 tons per year of particulate matter, 666.9 tons per year of volatile organic compounds, 664.7 tons per year of total HAPs, and 41,685 tons per year of carbon dioxide equivalents (greenhouse gases). No emission or equipment changes are being proposed by this action. The proposed Title V operating permit contains all applicable Federal and State regulatory requirements including monitoring, recordkeeping, and reporting conditions. The emission restriction, testing, monitoring, recordkeeping, reporting and work practice conditions of the TVOP have been derived from the applicable requirements of 40 CFR Parts 52, 60, 63, 64, 68, 72, 73, 74, 75, 76, 96, 97, 98 and 25 Pa. Code Chapters 121—145.

 All pertinent documents used in the evaluation of the application are available for public review during normal business hours at the Department's Northcentral Regional office, 208 West Third Street, Suite 101, Williamsport, PA 17701. Appointments for scheduling a review must be made by calling 570-327-3693.

 Any person(s) wishing to provide the Department with additional information, which they believe should be considered prior to the issuance of this permit, may submit the information to the Department of Environmental Protection at the address shown in the preceding paragraph. A 30-day comment period from the date of this publication will exist for the submission of comments. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit (specify Permit No. 55-00005) and concise statements regarding the relevancy of the information or objections to issuance of the permit.

 A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted based on the information received. All persons submitting comments or requesting a hearing will be notified of the decision to hold a hearing by publication in the newspaper or by the Pennsylvania Bulletin, or by telephone, where the Department of Environmental Protection determines such notification is sufficient. Written comments or requests for a public hearing should be directed to Muhammad Q. Zaman, Environmental Program Manager, Department of Environmental Protection, Air Quality Program, Northcentral Regional Office, 208 West Third Street, Suite 101, Williams-port, PA 17701, 570-327-3648.

41-00005: Lycoming Engines. (652 Oliver Street, Williamsport, PA 17701) to issue a renewal Title V operating permit for their facility located in the City of Williamsport, Lycoming County. The facility is currently operating under Title V Operating Permit 41-00005. The facility's main sources include engine testing, surface coating, and degreasing/cleaning operations. The facility also operates one Perchloroethylene Degreaser and numerous storage tanks and small natural gas-fired combustion units. The facility has potential emissions of 3,567 tons per year of carbon monoxide, 65.8 tons per year of nitrogen oxides, 3.4 tons per year of sulfur oxides, 7.3 tons per year of particulate matter, 67.4 tons per year of volatile organic compounds, 9.9 tons per year of any hazardous air pollutant (HAP), 24.9 tons per year of total HAPs, 1.7 tons per year of lead, and 63,425 tons per year of carbon dioxide equivalents (greenhouse gases). No emission or equipment changes are being proposed by this action. The proposed Title V operating permit contains all applicable Federal and State regulatory requirements including monitoring, recordkeeping, and reporting conditions. The emission restriction, testing, monitoring, recordkeeping, reporting and work practice conditions of the TVOP have been derived from the applicable requirements of 40 CFR Parts 52, 60, 63, 64, 68, 72, 73, 74, 75, 76, 96, 97, 98 and 25 Pa. Code Chapters 121—145.

 All pertinent documents used in the evaluation of the application are available for public review during normal business hours at the Department's Northcentral Regional office, 208 West Third Street, Suite 101, Williamsport, PA 17701. Appointments for scheduling a review must be made by calling 570 327 3693.

 Any person(s) wishing to provide the Department with additional information, which they believe should be considered prior to the issuance of this permit, may submit the information to the Department of Environmental Protection at the address shown in the preceding paragraph. A 30-day comment period from the date of this publication will exist for the submission of comments. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit (specify Permit No. 41-00005) and concise statements regarding the relevancy of the information or objections to issuance of the permit.

 A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted based on the information received. All persons submitting comments or requesting a hearing will be notified of the decision to hold a hearing by publication in the newspaper or by the Pennsylvania Bulletin, or by telephone, where the Department of Environmental Protection determines such notification is sufficient. Written comments or requests for a public hearing should be directed to Muhammad Q. Zaman, Environmental Program Manager, Department of Environmental Protection, Air Quality Program, Northcentral Regional Office, 208 West Third Street, Suite 101, Williamsport, PA 17701, 570 327 3648.

49-00020: Truck Accessories Group LLC—d/b/a TAG East (3560 Housels Run Road, Milton, PA 17847) a Title V operating permit renewal for their Milton facility located in Milton Borough, Northumberland County. In accordance with 25 Pa. Code § 127.521, the Department of Environmental Protection (DEP) has received an application and intends to issue a renewal of an Air Quality Operating Permit for the abovementioned facility. The subject facility has the following potential emissions: 9.97 tons per year (TPY) of CO; 7.26 TPY of NOx; 0.05 TPY of SOx; 1.80 TPY of PM/PM10; 188.36 TPY of VOC; 91.62 TPY of total HAPs and 10,672 TPY of CO2e. The facility's sources include forty-three (43) natural gas-fired space heaters, one (1) propane-fired emergency generator, a fiberglass reinforced plastic molding and assembly operation, a truck cap and Tonneau Cover assembly and finishing area, aluminum truck cap assembly and finishing area and three (3) solvent recovery units. The Department has determined that the sources at the facility satisfy best available technology (BAT) requirements, pursuant to 25 Pa. Code §§ 127.1 and 127.12, as well as the National Emission Standards for Hazardous Air Pollutants for Surface Coating of Plastic Parts and Products, 40 CFR 63.4480 through 63.4581; National Emission Standards for Hazardous Air Pollutants for Reinforced Plastic Composites Production, 40 CFR 63.4480 through 63.4581 and the National Emission Standards for Hazardous Air Pollutants for Stationary Reciprocating Internal Combustion Engines, 40 CFR 63.6580 through 63.6675. The proposed Title V operating permit contains all applicable Federal and State regulatory requirements including monitoring, recordkeeping, and reporting conditions. The emission restriction, testing, monitoring, recordkeeping, reporting and work practice conditions of the TVOP have been derived from the applicable requirements of 40 CFR Parts 52, 60, 63, 64, 68, 72, 73, 74, 75, 76, 96, 97, 98 and 25 Pa. Code Chapters 121—145.

 All pertinent documents used in the evaluation of the application are available for public review during normal business hours at the Department's Northcentral Regional office, 208 West Third Street, Suite 101, Williamsport, PA 17701. Appointments for scheduling a review must be made by calling 570 327 3693.

 Any person(s) wishing to provide the Department with additional information, which they believe should be considered prior to the issuance of this permit, may submit the information to the Department of Environmental Protection at the address shown in the preceding paragraph. A 30-day comment period from the date of this publication will exist for the submission of comments. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit (specify Permit No. TVOP 49-00020) and concise statements regarding the relevancy of the information or objections to issuance of the permit.

 A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted based on the information received. All persons submitting comments or requesting a hearing will be notified of the decision to hold a hearing by publication in the newspaper or by the Pennsylvania Bulletin, or by telephone, where the Department of Environmental Protection determines such notification is sufficient. Written comments or requests for a public hearing should be directed to Muhammad Q. Zaman, Environmental Program Manager, Department of Environmental Protection, Air Quality Program, Northcentral Regional Office, 208 West Third Street, Suite 101, Williamsport, PA 17701, 570 327 3648.

Northwest Region: Air Quality Program, 230 Chestnut Street, Meadville, PA 16335-3481

Contact: Matthew Williams, Facilities Permitting Chief—Telephone: 814-332-6131

25-00179: Erie City Sewer Authority (68 Port Access Road, Erie, PA 16507-2204), for the renewal of a Title V operating permit for the wastewater treatment plant located in the City of Erie, Erie County. The significant sources are two sewage sludge incinerators and two natural-gas/oil fired boilers, as well as 1 oil fueled and 3 natural-gas fueled emergency generators, a fuel oil storage tank, and five aeration tanks. The conditions of the previous plan approvals and operating permit were incorporated into the renewal permit. This facility is subject to the following federal regulations for which the applicable requirements are included in the permit renewal: 40 CFR Part 60 Subpart O, Standards of Performance for Sewage Treatment Plants; 40 CFR Part 60 Subpart MMMM, Emission Guidelines and Compliance Times for Existing Sewage Sludge Incineration Units; 40 CFR Part 61 Subpart C, National Emissions Standard for Beryllium; 40 CFR Part 61 Subpart E, National Emissions Standard for Mercury; 40 CFR Part 503 Subpart E, Standards for the Use or Disposal of Sewage Sludge—Incineration; 40 CFR Part 63 Subpart ZZZZ, NESHAP for Stationary Reciprocating Internal Combustion Engines. The potential emissions from the facility are as follows: 44.56 tpy PM; 175.63 typ NOx; 19.69 tpy SO2; 732.18 tpy CO; 29.91 tpy VOC, and 3.44 tpy Total HAPs.


Intent to Issue Operating Permits under the Air Pollution Control Act and 25 Pa. Code Chapter 127, Subchapter F.

Southeast Region: Air Quality Program, 2 East Main Street, Norristown, PA 19428

Contact: Janine Tulloch-Reid, Facilities Permitting Chief—Telephone: 484-250-5920

09-00083: HOP Energy, LLC—dba Brinker's Fuels, Inc. (445 North West Street, Doylestown, PA 18901) for renewal of a Non-Title V Facility, State-Only, Natural Minor Permit in Doylestown Borough, Bucks County. Brinker's Fuels, Inc. operates and maintains a bulk gasoline plant, underground gasoline storage tanks, and aboveground storage tanks for the storage of home heating oil, on-road diesel fuel, and off-road diesel fuel. Volatile organic compounds are the main emissions from this facility, and the facility has the potential to emit 5.8 tons of volatile organic compounds per year. The requirements of 40 C.F.R. Part 63, Subparts BBBBBB and CCCCCC were found to apply to the bulk gasoline plant and the gasoline dispensing operations of this facility, and the applicable requirements from these regulations were added to the permit. Monitoring, record keeping and reporting requirements have been added to the permit to address applicable limitations.

Northeast Region: Air Quality Program, 2 Public Square, Wilkes-Barre, PA 18711-0790

Contact: Ray Kempa, New Source Review Chief—Telephone: 570-826-2507

39-00064: Cera-Met (2175 Avenue C, Bethlehem, PA 18017-2119) to issue a renewal State Only (Synthetic Minor) Operating Permit to an aluminum castings facility located in Bethlehem City, Lehigh County. The sources at the facility include aluminum casting process equipment (mixing tanks, shell room, autoclave, burnout / preheat ovens, work benches, media blast cabinets, melting / holding ovens). The sources have the potential to emit volatile organic compounds (VOCs) above Title V thresholds. The permittee shall demonstrate compliance by use of a wet scrubber and thermal oxidizer control devices to keep VOC emissions below the Title V limit. The proposed State Only (Synthetic Minor) Operating Permit contains applicable requirements for emissions limitations, monitoring, record keeping, reporting, and work practice standards used to ensure facility compliance with Federal and State air pollution regulations.

39-00072: Hamilton 9999 Association LP (9999 Hamilton Boulevard, Breinigsville, PA 18031-9359) for an electronic manufacturing facility in Upper Macungie Township, Lehigh County. The facility's main sources include three natural gas/#2 fuel fired boilers. The facility has potential to emit PM, VOCs, HAPs, NOx, SOx and CO below the major emission thresholds. The proposed State-only Operating Permit contains applicable requirements for emissions limitations, monitoring, recordkeeping, reporting and work practice standards designed to ensure facility compliance with Federal and State air pollution regulations. This is a renewal State-Only Synthetic Minor operating permit.

54-00002: Honeywell International, Inc. (98 Westwood City of Bethlehem, Lehigh County Road, Pottsville, PA 17901-1834) to issue a renewal State Only (Synthetic Minor) Operating Permit for a plastics, film and sheet manufacturing facility in Norwegian Township, Schuylkill County. The facility sources include: eight (8) film extrusion lines, three (3) pellet die equipment sources, one (1) coater, two (2) ovens, two (2) oil heaters, one (1) pelletizer/powder conveyor system and one (1) pelletizer conveyor table. These sources have the potential to emit major quantities of Volatile Organic Compounds (VOCs) above Title V emission thresholds. The facility is taking a limitation on production throughput in order to keep VOCs under the Title V limit. The proposed State Only Operating Permit contains all applicable requirements including Federal and State regulations. In addition, monitoring, recordkeeping and reporting conditions regarding compliance with all applicable requirements are included.

Southcentral Region: Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110

Contact: Thomas J. Hanlon, Facility Permitting Chief—Telephone: 717-705-4862 or William Weaver, Program Manager—Telephone: 717-705-4702.

22-03037: Consolidated Scrap Resources, Inc. (1616 North Cameron Street, P. O. Box 1761, Harrisburg, PA 17105) for operation of their metal scrap shredder and cyclone in the City of Harrisburg, Dauphin County. This is a renewal of their State-only operating permit issued in 2008.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue an Air Quality Operating Permit for the abovementioned facility.

 The subject facility has the potential-to-emit 0.1 tpy CO, 0.3 tpy NOx, 64.1 tpy PM10, 55.6 tpy PM2.5, 0.7 tpy SOx, 1.1 tpy VOC, 0.3 tpy of a single HAP (benzene), and 1.1 tpy combined HAPs. The operating permit will include emission limits and work practice standards along with monitoring and recordkeeping requirements to ensure the facility complies with the applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office, at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period, from the date of publication of this notice in the Pennsylvania Bulletin, will exist for the submission of comments or protests. Tom Hanlon, Facilities Permitting Chief, may be contacted at 717-705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

22-03065: Pennsylvania Department of Agriculture (2305 North Cameron Street, Harrisburg, PA 17110) for operation of the Pennsylvania Veterinary Laboratory (PVL), including a pathological waste incineratorin Susquehanna Township, Dauphin County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue a renewal of an Air Quality Operating Permit for the abovementioned facility.

 The subject facility has the potential-to-emit 12.4 tpy of NOx, 5.9 tpy of CO, 0.7 tpy of SOx, 0.9 tpy of PM, 0.6 tpy of VOCs, and 8,364 tpy of CO2e. The Operating Permit will include emission limits and work practice standards along with testing, monitoring, record keeping and reporting requirements to ensure the facility complies with all applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period from the date of publication of this notice in the Pennsylvania Bulletin will exist for the submission of comments or protests.

 Thomas Hanlon, Facilities Permitting Chief, may be contacted at 717-705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

36-03166: L & S Sweeteners (388 East Main Street, Leola, PA 17540) for operation of their liquid and dry bulk receiving and transfer facility located in West Earl Township, Lancaster County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue a renewal of an Air Quality Operating Permit for the abovementioned facility.

 The subject facility has the potential-to-emit 15.4 tpy of NOx, 8.4 tpy of CO, 0.5 tpy of SOx, 3.5 tpy of PM, 1.6 tpy of VOCs, and 2.1 tpy of HAPs. The Operating Permit will include emission limits and work practice standards along with testing, monitoring, record keeping and reporting requirements to ensure the facility complies with all applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period from the date of publication of this notice in the Pennsylvania Bulletin will exist for the submission of comments or protests.

 Thomas Hanlon, Facilities Permitting Chief, may be contacted at 717-705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

22-05003: Orograin Bakeries Manufacturing—Capitol Bakery (3996 Paxton Street, Harrisburg, PA 17111) for the operation of a bread baking facility in Swatara Township, Dauphin County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue an Air Quality Operating Permit for the abovementioned facility. Actual VOC emissions are estimated to be around 10.81 tpy (after control). The Operating Permit will include emission limits and work practice standards along with testing, monitoring, record keeping and reporting requirements to ensure the facility complies with all applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office, at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit identification of the proposed permit by the permit number listed above.

 A 30-day comment period, from the date of publication of this notice in the Pennsylvania Bulletin, will exist for the submission of comments or protests.

 Thomas J. Hanlon, Facilities Permitting Chief, may be contacted at (717) 705-4862, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

36-03124: Reading Group, LLC. (1363 Bowmansville Road, Bowmansville, PA 17057) for operation of their custom truck assembly facility in Brecknock Township, Lancaster County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue a State Only Air Quality Operating Permit renewal for the above mentioned facility.

 The actual emissions in year 2012 from the operation were 1.1 tons of VOC per year. The Operating Permit will include emission limits and work practice standards along with monitoring, recordkeeping and reporting requirements to ensure the facility complies with the applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Southcentral Regional Office, at 909 Elmerton Avenue, Harrisburg, PA 17110.

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period, from the date of publication of this notice in the Pennsylvania Bulletin, will exist for the submission of comments or protests. A public hearing may be held, if the Department of Environmental Protection, in its discretion, decides that such a hearing is warranted based on the comments received.

 Gary Helsel, Acting New Source Review Chief, may be contacted at 814-949-7935, or at PA DEP Air Quality Program, 909 Elmerton Avenue, Harrisburg, PA 17110, for additional information or for the submission of comments or protests.

Northcentral Region: Air Quality Program, 208 West Third Street, Williamsport, PA 17701

Contact: Muhammad Q. Zaman, Environmental Program Manager—Telephone: 570-327-3648

41-00046: Pennsylvania College of Technology (One College Avenue, Williamsport, PA 17701) for their Williamsport campus located in the City of Williamsport, Lycoming County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received a renewal application and intends to issue a renewal Air Quality Operating Permit for the abovementioned facility. The subject facility has the following potential emissions: 36.94 TPY of NOx; 20.88 TPY of CO; 11.59 TPY of VOC; 3.06 TPY of PM10 and 90.14 TPY of SOx. The facility's main air contamination sources are natural gas/No. 2 fuel oil fired boilers, emergency generators and paint booths used for instructional purposes. The permittee has taken a restriction on the amount of No. 2 fuel oil permitted to be burned in order to become a synthetic minor facility. The operating permit will include emission limits and work practice standards along with monitoring, record keeping and reporting requirements to ensure the facility complies with all applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Northcentral Regional Office at 208 West Third Street, Suite 101, Williamsport, Pa 17701

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period from the date of publication of this notice in the Pennsylvania Bulletin will exist for the submission of comments or protests.

 Keith C. Allison, Chief, Facilities Permitting Section, may be contacted at 570-327-3640, or at PA DEP Air Quality Program, 208 West Third Street, Suite 101, Williamsport, Pa 17701, for additional information or for the submission of comments or protests.

17-00020: Glenn O. Hawbaker, Inc. (711 East College Avenue, Bellefonte, PA 16823) for their drum mix asphalt plant located in Sandy Township, Clearfield County.

 In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received a renewal application and intends to issue a renewal Air Quality Operating Permit for the abovementioned facility. The subject facility has the following potential emissions: 39.44 TPY of NOx; 81.32 TPY of CO; 20.44 TPY of VOC; 60.98 TPY of PM10 and 86.92 TPY of SOx, 5.37 TPY of HAPs. The facility's main air contaminations sources are drum mix plant, recycle asphalt paving equipment and parts washer. The permittee has taken an annual production throughput restriction of 1,230,000 tons to become a synthetic minor facility. The operating permit will include emission limits and work practice standards along with monitoring, record keeping and reporting requirements to ensure the facility complies with all applicable air quality regulations.

 Copies of the application, DEP's analysis and other documents used in the evaluation of the application are available for public review during normal business hours at the PA DEP Northcentral Regional Office at 208 West Third Street, Suite 101, Williamsport, Pa 17701

 A person may oppose the proposed operating permit, or may provide the Department with additional information to consider in its review, or may request a public hearing, by filing a written protest with the Department at the address listed above. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit by the permit number listed above and a concise statement regarding the relevancy of the information or objections to the issuance of the permit.

 A 30-day comment period from the date of publication of this notice in the Pennsylvania Bulletin will exist for the submission of comments or protests.

 Keith C. Allison, Chief, Facilities Permitting Section, may be contacted at 570-327-3640, or at PA DEP Air Quality Program, 208 West Third Street, Suite 101, Williamsport, Pa 17701, for additional information or for the submission of comments or protests.

Southwest Region: Air Quality Program, 400 Waterfront Drive, Pittsburgh, PA 15222-4745

Contact: Barbara Hatch, Facilities Permitting Chief—Telephone: 412-442-4174

04-00065: WHEMCO Steel Castings, Inc. (5 Hot Metal Street, Pittsburgh, PA 15203) for blast furnaces and iron and steel mills at the Midland Foundry in Midland Borough, Beaver County. This is a State Only Operating Permit Renewal application submittal.

30-00116: Columbia Gas Transmission Corp. (1700 MacCorkle Ave SE, Charleston, WV 25314-1518) In accordance with 25 Pa. Code §§ 127.424 and 127.425, the Department of Environmental Protection (DEP) is providing notice that they intend to issue a State Only Operating Permit (SOOP) Renewal to Columbia Gas to authorize the continued operation of the natural gas transmission facility known as the Waynesburg Station, located in Waynesburg Boro, Greene County.

 This facility consists of five (5) natural gas-fired turbine compressor engines each rated at 1,080 horsepower, an emergency generator (173 hp) with an operating hour limit of 500 hr/yr, a gas heating system boiler (0.75 MMBtu/hr), a heater (0.025 MMBtu/hr), and five (5) under/above ground tanks for the storage of pipeline liquids, lube oil and wastewater.

 This facility's potential to emit, on a rolling 12-month basis, is 19.2 tons of carbon monoxide, 63.0 tons of nitrogen oxides, 0.79 ton of volatile organic compounds, and 23,982 tons of carbon dioxide equivalents (greenhouse gases). The emission restriction, testing, monitoring, recordkeeping, reporting and work practice conditions of the proposed SOOP have been derived from the applicable requirements of 40 CFR Part 63-Subpart ZZZZ and 25 Pa. Code Chapters 121—145. No emission or equipment changes are being proposed by this action.

 Arrangements may be made to review the application at our offices. Those who wish to provide the Department with additional written information that they believe should be considered prior to the issuance of the Operating Permit renewal may written comments to Barbara Hatch, Pennsylvania Department of Environmental Protection, 400 Waterfront Drive, Pittsburgh, PA, 15222, 412-442-5226 (bhatch@pa.gov). A 30-day comment period, from the date of this publication, will exist for the submission of comments. Each written comment must contain the name, address and telephone number of the person submitting the comments, identification of the proposed permit (specify SOOP-30-00116) and concise statements regarding the relevancy of the information in the proposed permit or objections to issuance of the permit.

 A public hearing may be held, if DEP, in its discretion, decides that such a hearing is warranted based on the information received. All persons submitting comments or requesting a hearing will be notified of the decision to hold a hearing by publication in the newspaper or by the Pennsylvania Bulletin, or by telephone, where DEP determines such notification by telephone is sufficient. Written comments or requests for a public hearing should be directed to Barbara Hatch at the location identified above.

65-00817: Lindy Paving, Inc. / New Kensington Plant (201 Industrial Blvd. New Kensington, PA 15068) for the operation of a hot mix batch asphalt facility located in Lower Burrell City, Westmoreland County. In accordance with 25 Pa. Code §§ 127.424 and 127.425 the Department of Environmental Protection (DEP) has received an application and intends to issue an Air Quality Operating Permit for the above mentioned facility.

 The subject facility consists of one hot mix batch asphalt plants rated at 275 tons per hour. The batch plant is limited to 495,000 tons production in any consecutive 12-month period. The facility has the potential to emit: 99 tpy CO; 6.2 tpy NOx; 1.15 tpy SOx; 32.5 tpy VOC; 36.7 tpy PM and 6.7 tpy PM10. The facility is required to conduct annual burner tune up tests and stack testing for all criteria pollutants every five years. The facility must perform daily survey of the facility to ensure compliance with the operating permit limitations. The proposed authorization is subject to State and Federal Regulations. The permit includes operation requirements, monitoring requirements, and recordkeeping requirements.

 Those who wish to provide the Department with additional written information that they believe should be considered prior to the issuance of the Plan Approval may submit the information to Sheila Shaffer Pennsylvania Department of Environmental Protection, 400 Waterfront Drive, Pittsburgh, PA 15222. Written comments must contain the name, address and telephone number of the person submitting the comments, identification of the proposed Operating Permit (65-00817) and concise statements regarding the relevancy of the information or objections to issuance of the Operating Permit.

 All comments must be received prior to the close of business 30 days after the date of this publication.

Northwest Region: Air Quality Program, 230 Chestnut Street, Meadville, PA 16335-3481

Contact: Edward Orris, New Source Review Chief—Telephone: 814-332-6131

10-00337: Cellco Partnership Verizon Wireless Cranberry Call Center (700 Cranberry Woods Drive, Cranberry Township, PA 16066-5213), for a renewal of the operating permit for the facility located in Cranberry Township, Butler County. The facility has a 2000 kW emergency generator that is fueled with low sulfur diesel (less than 0.3 percent sulfur by weight). The conditions of the previous plan approval and operating permit were incorporated into the renewal permit. The emergency generator is restricted to 500 hours of operation and shall only be operated during utility power outages and for periodic maintenance testing. The emergency generators are subject to 40 CFR 63 Subpart ZZZZ—NESHAP for Reciprocating Internal Combustion Engine (RICE). The facility is a Natural Minor.

33-00116: Macdonald and Owen Lumber Co. (11424 Route 36, Brookville, PA 15825-8656), for the renewal of a Natural Minor Permit to operate a lumber processing plant located in Rose Township, Jefferson County. The facility's major emitting sources included, 1) Wood burning steam boiler, 2) 200 HP Boiler, 3) Grinder and, 4) Eight wood-drying kilns. The emissions from the facility are less than the Title V emission threshold. Thus, the facility is natural minor. The biomass fueled boilers are subject to area source boiler MACT 40 CFR Part 63, Subpart JJJJJJ. The actual emissions from the facility are PM: 6.57 Tons per year (TPY), CO: 14.15 TPY and, NOx: 11.52 TPY.

61-00122: Seneca Hardwood Lumber/Cranberry Facility (212 Seneca Hardwood Drive, Cranberry, PA 16319-2526), for the re-issuance of a Natural Minor Operating Permit located in Rockland Township, Venango County. The facility's major sources of emissions are two (2) Wood-Fired Boilers used to produce heat for the kiln operations. All emissions of criteria pollutants are below major source thresholds. The boilers at this facility will be subject to the requirements of 40 CFR Part 63, Subpart JJJJJJ—National Emission Standards for Hazardous Air Pollutants for Industrial, Commercial, and Institutional Boilers Area Sources. The compliance date for this subpart is March 21, 2014.

Department of Public Health, Air Management Services: 321 University Avenue, Philadelphia, PA 19104

Contact: Edward Wiener, Chief—Telephone: 215-685-9426

N12-013: SJA Construction, Inc. (at 2870 E. Allegheny Ave Philadelphia, PA 19134) for operating a 2.8 MMBTu/hr boiler, a mixer, a Baghouse and Cement Silo, in the City of Philadelphia, Philadelphia County.

 The operating permit will be issued under 25 Pa. Code, Philadelphia Code Title 3 and Air Management Regulation XIII. Permit copies and other supporting information are available for public inspection at AMS, 321 University Avenue, Philadelphia, PA 19104. For further information, contact Edward Wiener at (215) 685-9426.

 Persons wishing to file protest or comments on the above operating permit must submit the protest or comments within 30 days from the date of this notice. Any protests or comments filed with AMS must include a concise statement of the objections to the permit issuance and the relevant facts upon which the objections are based. Based upon the information received during the public comment period, AMS may modify the operating permit or schedule a public hearing. The hearing notice will be published in the Pennsylvania Bulletin and a local newspaper at least thirty days before the hearing.

S12-039: Southern Graphics Systems (2781 Roberts Ave, Philadelphia, PA 19129), for manufacturing of printing plates for the flexographic printing industry in the City of Philadelphia, Philadelphia County. The synthetic minor facility's air emission sources include three (3) photo processing units, three (3) plate dryers, and two (2) distillation stills.

 The operating permit will be issued under 25 Pa. Code, Philadelphia Code Title 3 and Air Management Regulation XIII. Permit copies and other supporting information are available for public inspection at AMS, 321 University Avenue, Philadelphia, PA 19104. For further information, contact Edward Wiener at (215) 685-9426.

 Persons wishing to file protest or comments on the above operating permit must submit the protest or comments within 30 days from the date of this notice. Any protests or comments filed with AMS must include a concise statement of the objections to the permit issuance and the relevant facts upon which the objections are based. Based upon the information received during the public comment period, AMS may modify the operating permit or schedule a public hearing. The hearing notice will be published in the Pennsylvania Bulletin and a local newspaper at least thirty days before the hearing.