NOTICES

DEPARTMENT OF ENVIRONMENTAL PROTECTION

Applications, Actions and Special Notices


APPLICATIONS

[33 Pa.B. 5935]

THE CLEAN STREAMS LAW AND THE FEDERAL CLEAN WATER ACT

APPLICATIONS FOR NATIONAL POLLUTION DISCHARGE ELIMINATION SYSTEM (NPDES) PERMITS AND WATER QUALITY MANAGEMENT (WQM) PERMITS

   This notice provides information about persons who have applied for a new, amended or renewed NPDES or WQM permit, a permit waiver for certain stormwater discharges or submitted a Notice of Intent (NOI) for coverage under a General Permit. The applications concern, but are not limited to, discharges related to industrial, animal or sewage waste, discharges to groundwater, discharges associated with municipal separate storm sewer systems (MS4), stormwater associated with construction activities or concentrated animal feeding operations (CAFOs). This notice is provided in accordance with 25 Pa. Code Chapters 91 and 92 and 40 CFR Part 122, implementing The Clean Streams Law (35 P. S. §§ 691.1--691.1001) and the Federal Clean Water Act.

Location Permit Authority Application Type or Category
Section I NPDES Renewals
Section II NPDES New or amendment
Section III WQM Industrial, sewage or animal waste; discharge into groundwater
Section IV NPDES MS4 individual permit
Section V NPDES MS4 permit waiver
Section VI NPDES Individual permit stormwater construction
Section VII NPDES NOI for coverage under NPDES general permits

   For NPDES renewal applications in Section I, the Department of Environmental Protection (Department) has made a tentative determination to reissue these permits for 5 years subject to effluent limitations and monitoring and reporting requirements in their current permits, with appropriate and necessary updated requirements to reflect new and changed regulations and other requirements.

   For applications for new NPDES permits and renewal applications with major changes in Section II, as well as applications for MS4 individual permits and individual stormwater construction permits in Sections IV and VI, the Department, based upon preliminary reviews, has made a tentative determination of proposed effluent limitations and other terms and conditions for the permit applications. These determinations are published as proposed actions for comments prior to taking final actions.

   Unless indicated otherwise, the EPA Region III Administrator has waived the right to review or object to proposed NPDES permit actions under the waiver provision in 40 CFR 123.24(d).

   Persons wishing to comment on an NPDES application are invited to submit a statement to the contact office noted before the application within 30 days from the date of this public notice. Persons wishing to comment on a WQM permit application are invited to submit a statement to the office noted before the application within 15 days from the date of this public notice. Comments received within the respective comment periods will be considered in the final determinations regarding the applications. Comments should include the name, address and telephone number of the writer and a concise statement to inform the Department of the exact basis of a comment and the relevant facts upon which it is based.

   The Department will also accept requests for a public hearing on applications. A public hearing may be held if the responsible office considers the public response significant. If a hearing is scheduled, a notice of the hearing will be published in the Pennsylvania Bulletin and a newspaper of general circulation within the relevant geographical area. The Department will postpone its final determination until after any public hearings are held.

   Persons with a disability who require an auxiliary aid, service, including TDD users, or other accommodations to seek additional information should contact the Department through the Pennsylvania AT&T Relay Service at (800) 654-5984.


I.  NPDES Renewal Applications

   Southeast Region: Water Management Program Manager, Lee Park, Suite 6010, 555 North Lane, Conshohocken, PA 19428.

NPDES Permit
No. (Type)
Facility Name and
Address
County and
Municipality
Stream Name
(Watershed No.)
EPA Waived
Y/N ?
PA0022586 North Wales Borough
300 School Street
North Wales, PA 19454
Montgomery County
North Wales Borough
UNT to Wissahickon Creek Y
PA0040576 Valleybrook Homeowner's Association
P. O. Box 394
Chester Heights, PA 19017
Delaware County
Chester Heights Borough
West Branch Chester Creek Y

   Northeast Region: Water Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18711-0790.
NPDES Permit
No. (Type)
Facility Name and
Address
County and
Municipality
Stream Name
(Watershed No.)
EPA Waived
Y/N ?
PA0060895
Sewage
Pocono Mountain Industries, Inc.
556 Main Street
Stroudsburg, PA 18360
Monroe County
Coolbaugh Township
Unnamed tributary to Red Run
2A
Y
PA0063827
Sewage
James and Judy Saunders
14 All King's Drive
New Ringgold, PA 17960
Schuylkill County
West Penn Township
Unnamed tributary to Lizard Creek
2B
Y
PA0061786 Manwalamink Sewer Company
River Road--Fort DePuy
P. O. Box 93
Shawnee-on-Delaware, PA 18356-0093
Monroe County
Smithfield Township
Brodhead Creek
1E
Y

   Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110, (717) 705-4707.
NPDES Permit
No. (Type)
Facility Name and
Address
County and
Municipality
Stream Name
(Watershed No.)
EPA Waived
Y/N ?
PA0110744
IW
City of Cumberland
Evitts Creek Water Co.
1032 Lake Gordon Road
Bedford, PA 15522
Bedford County
Cumberland Valley Township
Evitts Creek
13-A
Y
PA0083917
IW--Transfer
Edge Rubber
811 Progress Road
Chambersburg, PA 17201
Franklin County
Chambersburg Borough
Dry Swale Conocheague Creek
13-C
Y

II.  Applications for New or Expanded Facility Permits, Renewal of Major Permits and EPA Nonwaived Permit Applications

   Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110, (717) 705-4707.

   PA0043257 Amendment No. 1, Sewage, SIC Code 4952, New Freedom Borough Authority, 49 East Main Street, New Freedom, PA 17349. This facility is in Railroad Borough, York County.

   Description of activity: Amendment of an NPDES permit for existing discharge of treated sewage from a sequencing batch reactor facility.

   The receiving stream, South Branch Codorus Creek, is in Watershed 7-H and classified for WWF, water supply, recreation and fish consumption. The nearest downstream public water supply intake is for the York Water Company on the South Branch Codorus Creek, approximately 19 miles downstream. The discharge is not expected to affect the water supply.

   The proposed final effluent limitations for Outfall 001 based on a design flow of 2.25 MGD are:

Mass (lbs/day) Concentration (mg/l)
AverageAverageMaximumAverageAverageMaximumInstantaneous
ParameterMonthly Weekly Daily Monthly Weekly Daily Maximum
pH (S.U.) XXX XXX XXX from 6.0 to 9.0 inclusive
Dissolved Oxygen XXX XXX XXX minimum of 5.0 mg/l at all times
Total Residual Chlorine
   (Interim) XXX XXX XXX 0.31 XXX Monitor and Report 0.84
   (Final) XXX XXX XXX 0.2 XXX Monitor and Report 0.66
Total Suspended Solids 563 844 XXX 30 45 XXX 60
CBOD5 469 751 XXX 25 40 XXX 50
NH3-N
   (5-1 to 10-31) 19 XXX XXX 1.0 XXX XXX 2.0
   (11-1 to 4-30) 56 XXX XXX 3.0 XXX XXX 6.0
Total Phosphorus 37.5 XXX XXX 2.0 XXX XXX 4.0
Total Nitrogen XXX XXX XXX XXX XXX Monitor and Report XXX
Fecal Coliform
   (5-1 to 9-30) XXX XXX XXX 200/100 ml as a geometric mean
   (10-1 to 4-30) XXX XXX XXX 2,000/100 ml as a geometric mean
Total Copper
   (Interim) XXX XXX XXX XXX XXX Monitor and Report XXX
   (Final) XXX XXX XXX 0.012 XXX 0.024 0.03
Bis(2-ethylhexyl)phthalate
   (Interim) XXX XXX XXX XXX XXX Monitor and Report XXX
   (Final) XXX XXX XXX 0.0029 XXX 0.0058 0.0072

   In addition to the effluent limits, the permit contains the following major special conditions: Quarterly Whole Effluent Toxicity Testing; continuous instream monitoring downstream from discharge; and equalization of discharge to receiving stream.

   Individuals may make an appointment to review the Department files on this case by calling the File Review Coordinator at (717) 705-4732.

   The EPA waiver is not in effect.

   PA0247227, Sewage, Dublin Township Supervisors, 29195 Great Cove Road, Fort Littleton, PA 17223. This facility is in Dublin Township, Fulton County.

   Description of activity: Issuance of an NPDES permit for new discharge of treated sewage.

   The receiving stream, South Branch Little Aughwick Creek, is in Watershed 12-C and classified for HQ-CWF, water supply, recreation and fish consumption. The nearest downstream public water supply intake for Newport Borough is on the Juniata River, more than 50 miles downstream. The discharge is not expected to affect the water supply.

   The proposed effluent limits for Outfall 001 for a design flow of 0.018 MGD are:

AverageAverageInstantaneous
ParameterMonthly (mg/l) Weekly (mg/l) Maximum (mg/l)
CBOD5 10 15 20
Total Suspended Solids 10 15 20
NH3-N
   (5-1 to 10-31)1.53.0
   (11-1 to 4-30)4.59.0
Total Phosphorus 1.0 2.0
Dissolved Oxygen minimum of 5.0 at all times
pH from 6.0 to 9.0 inclusive
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric average
   (10-1 to 4-30) 200/100 ml as a geometric average

   Individuals may make an appointment to review the Department files on this case by calling the File Review Coordinator at (717) 705-4732.

   The EPA waiver is in effect.


   Southwest Region: Water Management Program Manager, 400 Waterfront Drive, Pittsburgh, PA 15222-4745.

   PA0026581, Sewage, Westmoreland Fayette Municipal Sewage Authority, P. O. Box 126, Scottdale, PA 15683. This application is for renewal of an NPDES permit to discharge treated sewage from Scottdale STP in Scottdale Borough, Westmoreland County.

   The following effluent limitations are proposed for discharge to the receiving waters, known as Jacobs Creek, which are classified as a WWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the McKeesport Municipal Water Authority.

   Outfall 001: existing discharge, design flow of 1.6 mgd.

Concentration (mg/l)
Average Average Maximum Instantaneous
Parameter Monthly Weekly Daily Maximum
CBOD5
   (5-1 to 10-31) 20 30 40
   (11-1 to 4-30) 25 38 50
Suspended Solids 30 45 60
Ammonia Nitrogen
   (5-1 to 10-31) 4.5 6.5 9.0
   (11-1 to 4-30) 13.5 20.0 27.0
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric mean
   (10-1 to 4-30) 2,000 as a geometric mean
Total Residual Chlorine
   (37th month to Expiration) .5 1.6
Dissolved Oxygen not less than 5.0 mg/l
pH not less than 6.0 nor greater than 9.0

   Other Conditions Outfalls 004--011 will be permitted as combined sewage overflows.

   Outfalls SW1 and SW2 will be permitted to discharge uncontaminated stormwater runoff from the sewage treatment plant site.

   The EPA waiver is not in effect.

   PA0090981, Sewage, German Township, R. D. 1, Box 287, McClellandtown, PA 15458. This application is for renewal of an NPDES permit to discharge treated sewage from Footedale STP in German Township, Fayette County.

   The following effluent limitations are proposed for discharge to the receiving waters, known as unnamed tributary of Dunlap Creek, which are classified as a WWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Brownsville Water Company.

   Outfall 001: existing discharge, design flow of 0.085 mgd.

Concentration (mg/l)
Average Average Maximum Instantaneous
Parameter Monthly Weekly Daily Maximum
CBOD52550
Suspended Solids 30 60
Ammonia Nitrogen
   (5-1 to 10-31) 5.5 11.0
   (11-1 to 4-30) 16.5 33.0
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric mean
   (10-1 to 4-30) 6,000/100 ml as a geometric mean
Total Residual Chlorine 1.3 3.1
pH not less than 6.0 nor greater than 9.0

   The EPA waiver is in effect.

   PA0096211, Sewage, Hempfield Township Municipal Authority, R. D. 6, Box 501, Greensburg, PA 15601. This application is for renewal of an NPDES permit to discharge treated sewage from Darragh Sewage Treatment Plant in Hempfield Township, Westmoreland County.

   The following effluent limitations are proposed for discharge to the receiving waters, known as Little Sewickley Creek, which are classified as a TSF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Westmoreland County Municipal Authority, McKeesport Plant, on the Youghiogheny River.

   Outfall 001: existing average design flow of 0.15 mgd, effective until the sewage treatment plant expansion is completed and operational.

Concentration (mg/l)
Average Average Maximum Instantaneous
Parameter Monthly Weekly Daily Maximum
CBOD5 25 38 50
Suspended Solids 30 45 60
Ammonia Nitrogen
   (5-1 to 10-31) 4.5 6.8 9.0
   (11-1 to 4-30) 13.5 20.3 27.0
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric mean
   (10-1 to 4-30) 6,500/100 ml as a geometric mean
Total Residual Chlorine Monitor and Report
pH not less than 6.0 nor greater than 9.0

   Outfall 001: proposed average design flow of 1.12 mgd, effective after the sewage treatment plant expansion is completed and operational.

Concentration (mg/l)
Average Average Maximum Instantaneous
Parameter Monthly Weekly Daily Maximum
CBOD5
   (5-1 to 10-31) 15 23 30
   (11-1 to 4-30) 25 38 50
Suspended Solids 30 45 60
Ammonia Nitrogen
   (5-1 to 10-31) 2.0 3.0 4.0
   (11-1 to 4-30) 6.0 9.0 12.0
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric mean
   (10-1 to 4-30) 2,000/100 ml as a geometric mean
Dissolved Oxygen not less than 6.0 mg/l
Copper Monitor and Report
pH not less than 6.0 nor greater than 9.0

   The EPA waiver is in effect.

   PA0203688, Sewage, West Pike Run Township Municipal Authority, 238 Pike Run Drive, Daisytown, PA 15427. This application is for renewal of an NPDES permit to discharge treated sewage from West Pike Run Township STP in West Pike Run Township, Washington County.

   The following effluent limitations are proposed for discharge to the receiving waters, known as Pike Run, which are classified as a TSF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Newell Municipal Water Authority.

   Outfall 001: existing discharge, design flow of 0.063 mgd.

Concentration (mg/l)
Average Average Maximum Instantaneous
Parameter Monthly Weekly Daily Maximum
CBOD5 25 50
Suspended Solids 30 60
Ammonia Nitrogen
   (5-1 to 10-31) 23.0 46.0
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric mean
   (10-1 to 4-30) 13,000/100 ml as a geometric mean
Total Residual Chlorine 1.4 3.3
pH not less than 6.0 nor greater than 9.0

   The EPA waiver is in effect.

   PA0204285, Sewage, Homer D. Reesman, 150 Reesman Court, Waynesburg, PA 15370. This application is for renewal of an NPDES permit to discharge treated sewage from the Reesman Mobile Home Park STP in Morgan Township, Greene County.

   The following effluent limitations are proposed for discharge to the receiving waters, known as tributary of South Fork Tenmile Creek, which are classified as a WWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Tri County Joint Municipal Authority.

   Outfall 001: existing discharge, design flow of 0.034 mgd.

Concentration (mg/l)
Average Average Maximum Instantaneous
Parameter Monthly Weekly Daily Maximum
CBOD5 25 50
Suspended Solids 30 60
Ammonia Nitrogen
   (5-1 to 10-31) 1.9 3.8
   (11-1 to 4-30) 3.0 6.0
Fecal Coliform
   (5-1 to 9-30) 200/100 ml as a geometric mean
   (10-1 to 4-30) 2,000/100 ml as a geometric mean
Total Residual Chlorine 0.02 0.05
Dissolved Oxygen not less than 5 mg/l
pH not less than 6.0 nor greater than 9.0

   The EPA waiver is in effect.


III. WQM Industrial Waste and Sewerage Applications under The Clean Streams Law (35 P. S. §§ 691.1--691.1001)

   Southeast Region: Water Management Program Manager, Lee Park, Suite 6010, 555 North Lane, Conshohocken, PA 19428.

   WQM Permit No. 1503425, Sewerage, Valley Township, 890 W. Lincoln Highway, P. O. Box 467, Coatesville, PA 19320. This proposed facility is in Valley Township, Chester County.

   Description of Proposed Action/Activity: Construction and operation of an age qualified residential community of 621 units and a community center.

   WQM Permit No. 1503426, Sewerage, Upper Uwchlan Township Municipal Authority, 140 Pottstown Pike, Chester Springs, PA 19425. This proposed facility is in Upper Uwchlan Township, Chester County.

   Description of Proposed Action/Activity: Construction and operation of a sanitary pump station.

   Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110, (717) 705-4707.

   WQM Permit No. 2803406, Sewerage, Findlay Park, LLP, 930 N. East Street, Suite 7, Frederick, MD 21701. This proposed facility is in Mercersburg Borough and Peters Township, Franklin County.

   Description of Proposed Action/Activity: Construction of a pump station to serve the Findlay Park.

   WQM Permit No. 5003404, Sewerage, Edna J. Bishop, 1882 Orchard Road, Chambersburg, PA 17201. This proposed facility is in Southwest Madison Township, Perry County.

   Description of Proposed Action/Activity: Construction of a sewage treatment facility to serve a single family residence.

   Northwest Region: Water Management Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481.

   WQM Permit No. 2503430, Sewerage, Erie County c/o Doug Range, Erie County Department of Health, 606 West Second Street, Erie, PA 16507. This proposed facility is in Various Municipalities, Erie County.

   Description of Proposed Action/Activity: A single residence sewage treatment plant.


IV.  NPDES Applications for Stormwater Discharges from MS4


V.  Applications for NPDES Waiver Stormwater Discharges from MS4


VI.  NPDES Individual Permit Applications for Discharges of Stormwater Associated with Construction Activities

   Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110.

NPDES Permit No. Applicant Name and
Address
County Municipality Receiving
Water/Use
PAI033603007 Solanco School District
121 South Hess Street
Quarryville, PA 17566
Lancaster East Drumore Township
UNT to Stewart Run
HQ-CWF, MF

   Northcentral Region: Water Management Program Manager, 208 West Third Street, Williamsport, PA 17701.

   Clinton County Conservation District: 45 Cooperation Lane, Mill Hall, PA 17751, (570) 726-3798.

NPDES Permit No. Applicant Name and
Address
County Municipality Receiving
Water/Use
PAI041803005 Lock Haven University
Health Professional
Parking Lot
301 W. Church St.
Room 104
Lock Haven, PA 17745
Clinton Lock Haven City
West Branch Susquehanna River
WWF

VII.  List of NOIs for NPDES and/or Other General Permit Types

PAG-12 CAFOs
PAG-13 Stormwater Discharges from MS4

MS4 Notices of Intent Received

   Northeast Region: Water Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18711-0790.

NPDES Permit No. Applicant Name and
Address
County Municipality Receiving Water/Use Department Protocol (Y/N)
PAG132209 Clarks Green Borough
104 N. Abington Rd.
Clarks Summit, PA 18411
Lackawanna Clarks Green Borough
Summit Lake Creek
TSF
Y
PAG132210 Dickson City Borough
801-805 Boulevard Ave.
Dickson City, PA 18519
Lackawanna Dickson City Borough Lackawanna River
CWF
Hull Creek
CWF
UNT to Lackawanna River
CWF
Y
PAG132212 Slatington Borough
125 S. Walnut St.
Slatington, PA 18080
Lehigh Slatington Borough Lehigh River
TSF
Trout Creek
CWF
UNT to Trout Creek
CWF
Y
PAG132230 Avoca Borough
752 Main St.
Avoca, PA 18641
Luzerne
Avoca BoroughMill Creek
CWF
Y

   Southwest Region: Water Management Program Manager, 400 Waterfront Drive, Pittsburgh, PA 15222-4745.

NPDES Permit No. Applicant Name and
Address
County Municipality Department Protocol (Y/N)
PAG136326 City of Arnold
1829 Fifth Avenue
Arnold, PA 15068
Westmoreland Arnold City Y
PAG136327 West Newton Borough
112 South Water Street
West Newton, PA 15089
Westmoreland West Newton Borough
Y
PAG136328 Derry Borough
114 East Second Avenue
Derry, PA 15627
Westmoreland Derry Borough Y
PAG136329 Latrobe City
P. O. Box 829
Latrobe, PA 15650
Westmoreland Latrobe City Y
PAG136330 Derry Township
650 Derry Road
Derry, PA 15627
Westmoreland Derry Township Y
PAG136331 Hempfield Township
R. D. 6 Box 500
Woodward Drive
Greensburg, PA 15601
Westmoreland Hempfield Township Y
PAG136332 Unity Township
1106 Beatty County Road
Latrobe, PA 15650
Westmoreland Unity Township Y
PAG136333 Ligonier Township
One Municipal Park Drive
Ligonier, PA 15658
Westmoreland Ligonier Township Y
PAG136334 City of Aliquippa
581 Franklin Avenue
Aliquippa, PA 15001
Beaver Aliquippa City Y
PAG136335 Patterson Heights Borough
510 8th Avenue
Beaver Falls, PA 15010
Beaver Patterson Heights Borough Y
PAG136336 Glenfield Borough
105 River Road
Sewickley, PA 15143
Allegheny Glenfield Borough Y
PAG136337 Bentleyville Borough
900 Main Street
Bentleyville, PA 15314
Washington Bentleyville Borough Y
PA1136117 West Taylor Township
712 Cooper Avenue
Johnstown, PA 15906
Cambria West Taylor Township Y

PUBLIC WATER SUPPLY (PWS) PERMIT

   Under the Pennsylvania Safe Drinking Water Act, the following parties have applied for a PWS permit to construct or substantially modify a public water system.

   Persons wishing to comment on a permit application are invited to submit a statement to the office listed before the application within 30 days of this public notice. Comments received within the 30-day comment period will be considered in the formulation of the final determinations regarding the application. Comments should include the name, address and telephone number of the writer and a concise statement to inform the Department of Environmental Protection (Department) of the exact basis of a comment and the relevant facts upon which it is based. A public hearing may be held after consideration of comments received during the 30-day public comment period.

   Following the comment period, the Department will make a final determination regarding the proposed permit. Notice of this final determination will be published in the Pennsylvania Bulletin at which time this determination may be appealed to the Environmental Hearing Board.

   The permit application and any related documents are on file at the office listed before the application and are available for public review. Arrangements for inspection and copying information should be made with the office listed before the application.

   Persons with a disability who require an auxiliary aid, service or other accommodations to participate during the 30-day public comment period should contact the office listed before the application. TDD users may contact the Department through the Pennsylvania AT&T Relay Service at (800) 654-5984.

SAFE DRINKING WATER


Applications Received under the Pennsylvania Safe Drinking Water Act (35 P. S. §§ 721.1--721.17)

   Northwest Region: Water Supply Management Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481.

   Permit No. 2703502, Public Water Supply.

Applicant Pennsylvania Suburban Water Company
Township or Borough Jenks Township, Forest County
Responsible Official Jack N. Walter, P. E.
Type of Facility PWS
Consulting Engineer Jack N. Walter, P. E.
Pennsylvania Suburban Water Company
644 North Water Avenue
Sharon, PA 16146
Application Received Date October 20, 2003
Description of Action Addition of Well 1A to Forest County SCI Water Treatment Facility for the completion and sanitary seal of the new source of supply and piping to connect to existing treatment facility.

   Southeast Region: Water Supply Management Program Manager, Lee Park, Suite 6010, 555 North Lane, Conshohocken, PA 19428.

   Permit No. 4603506, Public Water Supply.

Applicant Pennsylvania American Water Company
800 W. Hersheypark Drive
Hershey, PA 17033
Borough Royersford
Responsible Official Steven J. Seidl
800 W. Hersheypark Drive
Hershey, PA 17033
Type of Facility PWS
Consulting Engineer Pennsylvania American Water Company
Scott M. Thomas
800 W. Hersheypark Drive
Hershey, PA 17033
Application Received Date November 17, 2003
Description of Action Blasting and repainting the interior and exterior of an existing water storage tank.

[Continued on next Web Page]



No part of the information on this site may be reproduced for profit or sold for profit.

This material has been drawn directly from the official Pennsylvania Bulletin full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.