NOTICES
DEPARTMENT OF ENVIRONMENTAL PROTECTION
Applications, Actions and Special Notices
APPLICATIONS
[43 Pa.B. 4108]
[Saturday, July 20, 2013]
THE CLEAN STREAMS LAW AND THE FEDERAL CLEAN WATER ACT APPLICATIONS FOR NATIONAL POLLUTION DISCHARGE ELIMINATION SYSTEM (NPDES) PERMITS AND WATER QUALITY MANAGEMENT (WQM) PERMITS This notice provides information about persons who have applied for a new, amended or renewed NPDES or WQM permit, a permit waiver for certain stormwater discharges or submitted a Notice of Intent (NOI) for coverage under a General Permit. The applications concern, but are not limited to, discharges regarding industrial, animal or sewage waste, discharges to groundwater, discharges associated with municipal separate storm sewer systems (MS4), stormwater associated with construction activities or concentrated animal feeding operations (CAFO). This notice is provided in accordance with 25 Pa. Code Chapters 91 and 92a and 40 CFR Part 122, implementing The Clean Streams Law (35 P. S. §§ 691.1—691.1001) and the Federal Clean Water Act (33 U.S.C.A. §§ 1251—1376).
Location Permit Authority Application Type or Category Section I NPDES Renewals Section II NPDES New or Amendment Section III WQM Industrial, Sewage or Animal Waste; Discharge into Groundwater Section IV NPDES MS4 Individual Permit Section V NPDES MS4 Permit Waiver Section VI NPDES Individual Permit Stormwater Construction Section VII NPDES NOI for Coverage under NPDES General Permits For NPDES renewal applications in Section I, the Department of Environmental Protection (Department) has made a tentative determination to reissue these permits for 5 years subject to effluent limitations and monitoring and reporting requirements in their current permits, with appropriate and necessary updated requirements to reflect new and changed regulations and other requirements.
For applications for new NPDES permits and renewal applications with major changes in Section II, as well as applications for MS4 Individual Permits and Individual Stormwater Construction Permits in Sections IV and VI, the Department, based upon preliminary reviews, has made tentative determinations of proposed effluent limitations and other terms and conditions for the permit applications. In accordance with 25 Pa. Code § 92a.32(d), the proposed discharge of stormwater associated with construction activities will be managed in accordance with the requirements of 25 Pa. Code Chapter 102. These determinations are published as proposed actions for comments prior to taking final actions.
Unless indicated otherwise, the United States Environmental Protection Agency (EPA) Region III Administrator has waived the right to review or object to proposed NPDES permit actions under the waiver provision in 40 CFR 123.24(d).
Persons wishing to comment on NPDES applications are invited to submit statements to the contact office noted before the application within 30 days from the date of this public notice. Persons wishing to comment on WQM permit applications are invited to submit statements to the office noted before the application within 15 days from the date of this public notice. Comments received within the respective comment periods will be considered in the final determinations regarding the applications. A comment submittal should include the name, address and telephone number of the writer and a concise statement to inform the Department of the exact basis of a comment and the relevant facts upon which it is based.
The Department will also accept requests for public hearings on applications. A public hearing may be held if the responsible office considers the public response significant. If a hearing is scheduled, a notice of the hearing will be published in the Pennsylvania Bulletin and a newspaper of general circulation within the relevant geographical area. The Department will postpone its final determination until after a public hearing is held.
Persons with a disability who require an auxiliary aid, service, including TDD users, or other accommodations to seek additional information should contact the Department through the Pennsylvania AT&T Relay Service at (800) 654-5984.
I. NPDES Renewal Applications
Southeast Region: Clean Water Program Manager, 2 East Main Street, Norristown, PA 19401
NPDES No.
(Type)Facility Name &
AddressCounty & Municipality Stream Name
(Watershed No.)EPA Waived Y/N? PA0244384
(Sewage)Huntzinger SR STP
3947 Geryville Pike
Pennsburg, PA 18073-2618
Montgomery County
Marlborough TownshipUnnamed Tributary to Macoby Creek
(3-E)Y
Northeast Region: Clean Water Program Manager, 2 Public Square, Wilkes-Barre, PA 18701-1915. Phone: 570-826-2511.
NPDES No.
(Type)Facility Name &
AddressCounty & Municipality Stream Name
(Watershed No.)EPA Waived Y/N? PA0062936
(Industrial Waste)Lehighton Water Authority WTP
100 Maury Road
Lehighton, PA 18325
Carbon County
Franklin TownshipLong Run
(02B)Y PA0032999
(Sewage)Hickory Run State Park
RR 1, Box 81
White Haven, PA 18661-9712
Carbon County
Kidder TownshipHickory Run
HQ-CWF
(2A)
Y
Southcentral Region: Clean Water Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110. Phone: 717-705-4707.
NPDES No.
(Type)Facility Name &
AddressCounty & Municipality Stream Name
(Watershed #)EPA Waived Y/N? PA0083186
(Sew)HMS Host—Sideling Hill
Service Plaza
PO Box 8
Middletown, PA 17057
Fulton County / Taylor Township Dry Swale Lick Branch / 12-C Y PA0086550
(Sew)Jeffrey & Rose Siddens
65 Stonewall Lane
Alburtis, PA 18011
Berks County / Longswamp Township UNT Swabia Creek / 2-C Y
Northcentral Region: Clean Water Program Manager, 208 West Third Street, Williamsport, PA 17701
NPDES No.
(Type)Facility Name &
AddressCounty & Municipality Stream Name
(Watershed No.)EPA Waived Y/N? PA0113298
(Sewage)Elkland Borough Wastewater Treatment Plant
Ellison Road
Elkland, PA 16920
Tioga County
Elkland BoroughCowanesque River
(4-A)N PA0209376
(SFTF)Linda Geyer Apt
2713 Carson Hill Road
Dubois, PA 15801
Clearfield County
Brady TownshipUNT to Limestone Run Watershed #17D Y
Southwest Region: Water Management Program Manager, 400 Waterfront Drive, Pittsburgh, PA 15222-4745
NPDES No.
(Type)Facility Name &
AddressCounty & Municipality Stream Name
(Watershed #)EPA Waived Y/N PA0036609
SewageConway Boro
River Rd
Conway, PA 15027
Beaver Cnty
Conway BoroOhio River N
Northwest Region: Clean Water Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481
NPDES No.
(Type)Facility Name &
AddressCounty & Municipality Stream Name
(Watershed#)EPA Waived Y/N? PA0239224
(Sewage)Keystone Charter School
425 South Good Hope Road,
Greenville, PA 16125
Mercer County
West Salem TownshipBig Run
(20-A)Y
II. Applications for New or Expanded Facility Permits, Renewal of Major Permits and EPA Non-Waived Permit Applications
Southeast Region: Clean Water Program Manager, 2 East Main Street, Norristown, PA 19401
PA0052035, Sewage, SIC Code 4952, Upper Makefield Township, 1076 Eagle Road, Newtown, PA 18940-2818. Facility Name: Heritage Hills WWTP. This existing facility is located in Upper Makefield Township, Bucks County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Delaware River and Houghs Creek, is located in State Water Plan watershed 2-E and is classified for Warm Water Fishes and Migratory Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.172 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumInstant.
MinimumAverage
MonthlyInstant.
MaximumFlow (GPD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.23 XXX 0.45 CBOD5 14.3 XXX XXX 10 XXX 20 Total Suspended Solids 14.3 XXX XXX 10 XXX 20 Fecal Coliform (CFU/100 ml) XXX XXX XXX 200
Geo MeanXXX 1,000 Total Nitrogen XXX XXX XXX Report XXX XXX Ammonia-Nitrogen 4.3 XXX XXX 3.0 XXX 6.0 Total Phosphorus XXX XXX XXX Report XXX XXX The proposed effluent limits for Outfall 002 are based on a design flow of 0.159 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumInstant.
MinimumAverage
MonthlyInstant.
MaximumFlow (GPD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.23 XXX 0.45 CBOD5 13.3 XXX XXX 10 XXX 20 Total Suspended Solids 13.3 XXX XXX 10 XXX 20 Fecal Coliform (CFU/100 ml) XXX XXX XXX 200
Geo MeanXXX 1,000 Total Nitrogen XXX XXX XXX Report XXX XXX Ammonia-Nitrogen 4.0 XXX XXX 3.0 XXX 6.0 Total Phosphorus XXX XXX XXX Report XXX XXX In addition, the permit contains the following major special conditions:
• Designation of Responsible Operator
• No Stormwater
• Change in Ownership
• TRC Minimization
• Sludge Disposal
• Discharge During Emergency Situation
• Discharge to Groundwater Recharge Areas
• Discharge to Special Protection Waters
You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 484-250-5910.
The EPA Waiver is in effect.
PA0058556, SIC Code 4941, Downingtown Municipal Water Authority, 100 Water Plant Way, Downingtown, PA 19335-1951. Facility Name: Downingtown Municipal WFP. This existing facility is located in 100 Water Plant Way, Downingtown, PA 19335, Downingtown Borough, Chester County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated filter backwash, clarifier backwash, and sludge drying beds filtrate from sludge thickening/holding tank, from a Water Filtration Plant.
The receiving stream(s), Unnamed Tributary to East Branch Brandywine Creek, is located in State Water Plan watershed 3-H and is classified for Cold Water Fishes and Migratory Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.26 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Total Residual Chlorine XXX XXX XXX 0.5 1.0 1.25 Total Suspended Solids XXX XXX XXX 30 60 75 Total Dissolved Solids XXX XXX XXX 1,000 2,000 2,500 Total Phosphorus XXX XXX XXX Report Report XXX Total Aluminum XXX XXX XXX 4.0 8.0 10.0 Total Iron XXX XXX XXX 2.0 4.0 5.0 Total Manganese XXX XXX XXX 1.0 2.0 2.5 In addition, the permit contains the following major special conditions:
Part C Other Requirements:
A. Necessary Property Rights
B. Proper Sludge Disposal
C. BAT/BCT Reopener
D. Remedial Measures if Public Nuisance
E. Change in Ownership
F. TMDL/WLA Analysis
G. Laboratory Certification
You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 484-250-5910.
The EPA Waiver is in effect.
Southcentral Region: Clean Water Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110. Phone: 717-705-4707.PA0248193, SIC Code 6514, James K Adams Jr, 101 Shatto Drive, Carlisle, PA 17013. Facility Name: Adams Res. This proposed facility is located in North Middleton Township, Cumberland County.
Description of Proposed Activity: The application is to renew the NPDES permit for a discharge of treated sewage.
The receiving stream(s), Conodoguinet Creek, is located in State Water Plan watershed 7-B and is classified for Warm Water Fishes and Migratory Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.0005 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX Total Residual Chlorine XXX XXX XXX Report XXX XXX CBOD5 XXX XXX XXX 25 XXX 50 Total Suspended Solids XXX XXX XXX 30 XXX 60 Fecal Coliform (CFU/100 ml) XXX XXX XXX 200
Geo MeanXXX XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732. The EPA Waiver is in effect.
PA0087106, Sewage, SIC Code 8661, Freedom Valley Worship Center AOG, Inc., 3185 York Road, Gettysburg, PA 17325. Facility Name: Freedom Valley Worship Center STP. This existing facility is located in Straban Township, Adams County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated sewage.
The receiving stream(s), Unnamed Tributary to Swift Run, is located in State Water Plan watershed 7-F and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.002 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report XXX XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX CBOD5 XXX XXX XXX 10 XXX 20 Total Suspended Solids XXX XXX XXX 10 XXX 20 Fecal Coliform (CFU/100 ml) XXX XXX XXX 200
Geo MeanXXX XXX Ammonia-Nitrogen May 1 - Oct 31 XXX XXX XXX 6.0 XXX 12 Nov 1 - Apr 30 XXX XXX XXX 18 XXX 36 You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0247950, SIC Code 4952, James K Speed, 3461 Lower Glades Road, York, PA 17406. Facility Name: Speed Residence SRSTP. This existing facility is located in Springettsbury Township, York County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated sewage.
The receiving stream(s), Unnamed Tributary to Codorus Creek, is located in State Water Plan watershed 7-H and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.0004 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyMinimum Average
MonthlyInstant.
MaximumFlow (MGD) Report XXX XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Total Residual Chlorine XXX XXX XXX Report XXX XXX CBOD5 XXX XXX XXX 10 XXX 20 Total Suspended Solids XXX XXX XXX 10 XXX 20 Fecal Coliform (CFU/100 ml) XXX XXX XXX 200
Geo MeanXXX XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0008893, SIC Code 2621, Team Ten LLC, 1600 Pennsylvania Avenue, Tyrone, PA 16686-1758. Facility Name: Team Ten LLC Dba American Eagle Paper Mills. This existing facility is located in Tyrone Borough, Blair County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of non-contact cooling water.
The receiving stream(s), Bald Eagle Creek, is located in State Water Plan watershed 11-A and is classified for Trout Stocking, Trout Stocking and Migratory Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 10.1 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Temperature (°F) XXX XXX XXX Report Report XXX The proposed effluent limits for Outfall 002 are based on a design flow of 0.000000 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyMinimum Average
MonthlyInstant.
MaximumpH (S.U.) XXX XXX XXX XXX XXX Report CBOD5 XXX XXX XXX XXX XXX Report Chemical Oxygen Demand XXX XXX XXX XXX XXX Report Total Suspended Solids XXX XXX XXX XXX XXX Report Oil and Grease XXX XXX XXX XXX XXX Report Total Kjeldahl Nitrogen XXX XXX XXX XXX XXX Report Total Phosphorus XXX XXX XXX XXX XXX Report Dissolved Iron XXX XXX XXX XXX XXX Report The proposed effluent limits for Outfall 004 are based on a design flow of 0.000000 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyMinimum Average
MonthlyInstant.
MaximumpH (S.U.) XXX XXX XXX XXX XXX Report CBOD5 XXX XXX XXX XXX XXX Report Chemical Oxygen Demand XXX XXX XXX XXX XXX Report Total Suspended Solids XXX XXX XXX XXX XXX Report Oil and Grease XXX XXX XXX XXX XXX Report Total Kjeldahl Nitrogen XXX XXX XXX XXX XXX Report Total Phosphorus XXX XXX XXX XXX XXX Report Dissolved Iron XXX XXX XXX XXX XXX Report You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0081825, Sewage, SIC Code 4952, 6515, Betty Nelson, 14 Tip Top Circle, Carlisle, PA 17015. Facility Name: Betty Nelson MHP. This existing facility is located in Lower Frankford Township, Cumberland County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Conodoguinet Creek, is located in State Water Plan watershed 7-B and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.023 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.5 XXX 1.6 CBOD5 XXX XXX XXX 25 XXX 50 Total Suspended Solids XXX XXX XXX 30 XXX 60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 Total Nitrogen XXX XXX XXX Report
Annl AvgXXX XXX Total Phosphorus XXX XXX XXX 2.0 XXX XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0044911 A-1, SIC Code 2023, Land O Lakes Inc., 405 Park Drive, Carlisle, PA 17015-9270. Facility Name: Land O Lakes Carlisle Facility. This existing facility is located in South Middleton Township, Cumberland County.
Description of Existing Activity: The application is for amending an NPDES permit for an existing discharge of treated industrial waste.
The receiving stream(s), Mountain Creek, is located in State Water Plan watershed 7-E and is classified for Trout Stocking and Migratory Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.81 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Temperature (°F) Jul 1-31 XXX XXX XXX Report 93 XXX Aug 1 - Jun 30 XXX XXX XXX Report 110 XXX CBOD5 67 135 XXX 10 20 25 BOD5 Raw Sewage Influent Report Report XXX Report Report XXX Total Suspended Solids 67 135 XXX 10 20 25 Total Suspended Solids Raw Sewage Influent Report Report XXX Report Report XXX Ammonia-Nitrogen May 1 - Oct 31 10 20 XXX 1.5 3.0 3.7 Nov 1 - Apr 30 18.7 32 XXX 4.5 9.0 11 Total Phosphorus 6.7 13.5 XXX 1.0 2.0 2.5 You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0036889, Sewage, SIC Code 4952, Reading Township Municipal Authority, 5500 Carlisle Pike, New Oxford, PA 17350. Facility Name: Reading Township WWTP. This existing facility is located in Reading Township, Adams County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Conewago Creek, is located in State Water Plan watershed 7-F and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.33 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyWeekly
AverageInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.23 XXX 0.75 CBOD5 68 110
Wkly AvgXXX 25 40 50 BOD5 Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids 82 123
Wkly AvgXXX 30 45 60 Total Suspended Solids Raw Sewage Influent Report Report XXX Report XXX XXX Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1000 Oct 1 - Apr 30 XXX XXX XXX 2000
Geo MeanXXX 10000 Ammonia-Nitrogen May 1 - Oct 31 19 XXX XXX 7.0 XXX 14 Nov 1 - Apr 30 58 XXX XXX 21 XXX 42 Total Phosphorus 5.5 XXX XXX 2.0 XXX 4.0 The proposed monitoring requirements and, where appropriate, effluent limits for implementation of the Chesapeake Bay Tributary Strategy are as follows for Outfall 001.
Mass (lbs) Concentration (mg/l) Parameters Monthly Annual Minimum Monthly
AverageMaximum Ammonia—N Report Report XXX Report XXX Kjeldahl—N Report XXX XXX Report XXX Nitrate-Nitrite as N Report XXX XXX Report XXX Total Nitrogen Report Report XXX Report XXX Total Phosphorus Report Report XXX Report XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0261963, 312 NAICS Code, Shinn Spring Water Co., 2 East Pointe Drive, Birdsboro, PA 19508. Facility Name: East Pointe Bottling Plant. This proposed facility is located in Cumru Township, Berks County.
Description of Proposed Activity: The application is for a new NPDES permit for a new discharge of treated industrial wastewater.
The receiving stream(s), Schuylkill River, is located in State Water Plan watershed 3-C and is classified for Warm Water Fish, Migratory Fish, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.075 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Total Residual Chlorine XXX XXX XXX 0.5 XXX 1.6 Temperature (°F) XXX XXX XXX Report 110 XXX Total Suspended Solids 19 38 XXX 30 60 XXX Total Dissolved Solids 4,285 8,570 XXX 6,850 13,700 19,600 Oil and Grease 9.4 XXX XXX 15 XXX 30 Total Aluminum 2.5 5.0 XXX 4.0 8.0 XXX Total Iron 1.3 2.5 XXX 2.0 4.0 XXX Total Manganese 0.6 1.3 XXX 1.0 2.0 XXX Total Phosphorus Report XXX XXX Report XXX Report Sulfate XXX XXX XXX Report XXX Report Chloride XXX XXX XXX Report XXX Report PCBs (Dry Weather) (ng/L) XXX XXX XXX Report Report XXX PCBs (Wet Weather) (ng/L) XXX XXX XXX Report Report XXX Other significant conditions in the permit:
-The discharge is subject to Schuylkill River PCBs Total Maximum Daily Load (TMDL) as approved by U.S. EPA.
-The discharge of wastewater shall not increase the ambient temperatures of the receiving waters by more than 5°F, nor shall such discharge result in stream temperatures exceeding 87°F, outside of designated mixing zone.
You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0085600, SIC Code 3089, Ono Industries Inc., PO Box 150, Ono, PA 17077-0150. Facility Name: Ono Plastic Manufacturing. This existing facility is located in East Hanover Township, Lebanon County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated contact cooling water and stormwater.
The receiving stream(s), Unnamed Tributary to Reeds Creek, is located in State Water Plan watershed 7-D and is classified for Warm Water Fishes, Migratory Fishes and Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.057 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Temperature (°F) XXX XXX XXX XXX 87 XXX CBOD5 6.2 12.3 XXX 13 26 32 Total Suspended Solids 4.8 9.0 XXX 10 19 24 Oil and Grease 7.1 13.7 XXX 15 29 30 Total Nitrogen XXX XXX XXX Report
Annl AvgXXX XXX Total Phosphorus XXX XXX XXX Report
Annl AvgXXX XXX The proposed effluent limits for Outfall 002 are based on a design flow of 0.000000 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumpH (S.U.) XXX XXX XXX XXX XXX Report CBOD5 XXX XXX XXX XXX XXX Report Chemical Oxygen Demand XXX XXX XXX XXX XXX Report Total Suspended Solids XXX XXX XXX XXX XXX Report Oil and Grease XXX XXX XXX XXX XXX Report Total Kjeldahl Nitrogen XXX XXX XXX XXX XXX Report Total Phosphorus XXX XXX XXX XXX XXX Report Dissolved Iron XXX XXX XXX XXX XXX Report In addition, the permit contains the following major special conditions:
• BMPs added to control erosion and sediments
You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is in effect.
PA0033391, Sewage, SIC Code 6515, Frank T Perano, GSP Management Company, PO Box 677, Morgantown, PA 19543. Facility Name: Pine Manor MHP. This existing facility is located in Londonderry Township, Dauphin County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Unnamed Tributary to Lynch Run, is located in State Water Plan watershed 7-G and is classified for Trout Stocking and Migratory Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.02 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Annual
AverageDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report
Avg MoReport XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX .47 XXX 1.55 CBOD5 XXX XXX XXX 25 XXX 50 Total Suspended Solids XXX XXX XXX 30 XXX 60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 Nitrate-Nitrite as N Report XXX XXX Report
Annl AvgXXX XXX Total Nitrogen Report XXX XXX Report
Annl AvgXXX XXX Total Nitrogen XXX Report
Total AnnualXXX XXX XXX XXX Ammonia-Nitrogen May 1 - Oct 31 XXX XXX XXX 3.0 XXX 6.0 Nov 1 - Apr 30 XXX XXX XXX 9.0 XXX 18 Total Kjeldahl Nitrogen Report XXX XXX Report
Annl AvgXXX XXX Total Phosphorus Report
Avg MoXXX XXX 2.0 XXX 4.0 Total Phosphorus Report
Total MoXXX XXX XXX XXX XXX Total Phosphorus XXX 122
Total AnnualXXX XXX XXX XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA Waiver is not in effect.
Southwest Regional Office: Regional Manager, Clean Water, 400 Waterfront Drive, Pittsburgh, PA 15222-4745; 412-442-4000PA0035360, Sewage, SIC Code 4952, Plum Borough Municipal Authority, 4555 New Texas Road, Pittsburgh, PA 15239. Facility Name: Holiday Park STP. This existing facility is located in Plum Borough, Allegheny County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Abers Creek, is located in State Water Plan watershed 19-A and is classified for Trout Stocking, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 1.8 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 6.0 XXX XXX XXX CBOD5 May 1 - Oct 31 150 225
Wkly AvgXXX 10 15
Wkly Avg20 Nov 1 - Apr 30 374 561
Wkly AvgXXX 20 30
Wkly Avg40 BOD5 Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids Raw Sewage Influent Report Report XXX Report XXX XXX May 1 - Oct 31 376 563
Wkly AvgXXX 25 38
Wkly Avg50 Nov 1 - Apr 30 467 701
Wkly AvgXXX 25 38
Wkly Avg50 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 UV Transmittance (%) XXX XXX Report Report XXX XXX Total Nitrogen XXX XXX XXX XXX Report XXX Ammonia-Nitrogen May 1 - Oct 31 29 XXX XXX 1.9 XXX 3.8 Nov 1 - Apr 30 56 XXX XXX 3.0 XXX 6.0 Total Phosphorus XXX XXX XXX XXX Report XXX Total Aluminum XXX XXX XXX XXX Report XXX Total Copper May 1 - Oct 31 0.29 0.44 XXX 0.019 0.029 0.048 Nov 1 - Apr 30 0.35 0.54 XXX 0.019 0.029 0.048 Total Iron XXX XXX XXX XXX Report XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 412-442-4000.
The EPA Waiver is not in effect.
PA0026778, Sewage, Windber Area Authority, 1700 Stockholm Avenue, Windber, PA 15963. Facility Name: Ingleside STP. This existing facility is located in Richland Township, Cambria County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Stony Creek is located in State Water Plan watershed 18-E and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 4 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyWeekly
AverageMinimum Average
MonthlyWeekly
AverageInstant.
MaximumFlow (MGD) Report Report
Daily MaxXXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 4.0 XXX XXX XXX CBOD5 835 1,251 XXX 25 37.5 50 BOD5 Raw Sewage Influent Report Report
Daily MaxXXX Report XXX XXX Total Suspended Solids Raw Sewage Influent Report Report
Daily MaxXXX Report XXX XXX Total Suspended Solids 1,001 1,502 XXX 30 45 60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 UV Transmittance (mjoules/cm2) XXX XXX Report XXX XXX XXX Total Nitrogen XXX XXX XXX XXX Report
Daily MaxXXX Ammonia-Nitrogen May 1 - Oct 31 260 390 XXX 7.8 11.7 15.5 Nov 1 - Apr 30 767 1,151 XXX 23 34.5 46 Total Phosphorus XXX XXX XXX XXX Report
Daily MaxXXX The EPA Waiver is not in effect.
PA0023698, Sewage, SIC Code 4952, Vanport Township Municipal Authority, 285 River Avenue, Vanport, PA 15009. Facility Name: Vanport Water Pollution Control Plant. This existing facility is located in Vanport Township, Beaver County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Twomile Run, is located in State Water Plan watershed 20-B and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 2 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyWeekly
AverageMinimum Average
MonthlyWeekly
AverageInstant.
MaximumFlow (MGD) Report Report
Daily MaxXXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 4.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.5 XXX 1.6 CBOD5 325.5 488.2 XXX 25 37.5 50 BOD5 Raw Sewage Influent XXX XXX XXX Report XXX XXX Total Suspended Solids Raw Sewage Influent XXX XXX XXX Report XXX XXX Total Suspended Solids 390.5 585.8 XXX 30 45 60 Fecal Coliform (CFU/100 ml) May 1 - Oct 31 XXX XXX XXX 200
Geo MeanXXX 400 Nov 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 Total Nitrogen XXX XXX XXX XXX Report
Daily MaxXXX Ammonia-Nitrogen XXX XXX XXX Report XXX XXX Total Phosphorus XXX XXX XXX XXX Report
Daily MaxXXX The EPA Waiver is not in effect.
PA0038181, Sewage, SIC Code 4952, Hempfield Township Municipal Authority, 1146 Woodward Drive, Greensburg, PA 15601-6416. Facility Name: New Stanton STP. This existing facility is located in Hempfield Township, Westmoreland County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Sewickley Creek, is located in State Water Plan watershed 19-D and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 7.2 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX CBOD5 1,502 2,402
Wkly AvgXXX 25 40
Wkly Avg50 BOD5 Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids 1,802 2,703
Wkly AvgXXX 30 45
Wkly Avg60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 UV Transmittance (mjoules/cm2) XXX XXX Report Report XXX XXX Total Nitrogen XXX XXX XXX XXX Report XXX Ammonia-Nitrogen May 1 - Oct 31 210 XXX XXX 3.5 XXX 7.0 Nov 1 - Apr 30 510 XXX XXX 8.5 XXX 17.0 Total Phosphorus XXX XXX XXX XXX Report XXX Total Antimony (Interim) Report Report XXX Report Report XXX (Final) 0.46 0.71 XXX 0.0076 0.0118 0.019 Total Selenium (Interim) Report Report XXX Report Report XXX (Final) 0.40 0.63 XXX 0.0067 0.0105 0.01675 Bis(2-Ethylhexyl)Phthalate (Interim) Report Report XXX Report Report XXX (Final) 0.23 0.36 XXX 0.0038 0.0060 0.0095 You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 412-442-4000.
The EPA Waiver is not in effect.
PA0204994, Sewage, SIC Code 4952, Central Indiana County Joint Sewer Authority, PO Box 7, 603 South Main Street Ext., Homer City, PA 15748-0007. Facility Name: Homer City STP. This existing facility is located in Center Township, Indiana County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Two Lick Creek, is located in State Water Plan watershed 18-D and is classified for Trout Stocking, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.65 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 6.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.5 XXX 1.6 CBOD5 135.5 217
Wkly AvgXXX 25 40
Wkly Avg50 BOD5 Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids 163 244
Wkly AvgXXX 30 45
Wkly Avg60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 Total Nitrogen XXX XXX XXX XXX Report XXX Ammonia-Nitrogen May 1 - Oct 31 95 XXX XXX 17.5 XXX 35 Nov 1 - Apr 30 135.5 XXX XXX 25.0 XXX 50.0 Total Phosphorus XXX XXX XXX XXX Report XXX Total Aluminum XXX XXX XXX XXX Report XXX Total Iron XXX XXX XXX XXX Report XXX Total Manganese XXX XXX XXX XXX Report XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 412-442-4000.
The EPA Waiver is not in effect.
PA0025950, Sewage, SIC Code 4952, Municipal Authority of the City of Monongahela, 521 W Main Street, Monongahela, PA 15063-2615. Facility Name: City of Monongahela STP. This existing facility is located in Monongahela City, Washington County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated Sewage.
The receiving stream(s), Monongahela River, is located in State Water Plan watershed 19-C and is classified for Warm Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 1.5 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyDaily
MaximumMinimum Average
MonthlyDaily
MaximumInstant.
MaximumFlow (MGD) Report Report XXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 4.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.5 XXX 1.6 CBOD5 313 469
Wkly AvgXXX 25 40
Wkly Avg50 BOD5 Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids Raw Sewage Influent Report Report XXX Report XXX XXX Total Suspended Solids 376 563
Wkly AvgXXX 30 45
Wkly Avg60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 Total Nitrogen XXX XXX XXX XXX Report XXX Ammonia-Nitrogen Report XXX XXX Report XXX XXX Total Phosphorus XXX XXX XXX XXX Report XXX Chronic Toxicity - Pimephales Survival (TUc) XXX XXX XXX XXX 100.0 XXX Growth (TUc) XXX XXX XXX XXX 100.0 XXX You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 412-442-4000.
The EPA Waiver is not in effect.
Northwest Regional Office: Regional Clean Water Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481, Telephone: 814.332.6942.PA0020605, Sewage, SIC Code 4952, Union City Borough Municipal Authority, 29 South Main Street, Union City, PA 16438-1331. Facility Name: Union City STP. This existing facility is located in Union Township, Erie County.
Description of Existing Activity: The application is for a renewal of an NPDES permit for an existing discharge of treated sewage and stormwater.
The receiving stream(s), South Branch French Creek, is located in State Water Plan watershed 16-A and is classified for Cold Water Fishes, aquatic life, water supply and recreation. The discharge is not expected to affect public water supplies.
The proposed effluent limits for Outfall 001 are based on a design flow of 1.4 MGD.
Mass (lb/day) Concentration (mg/l) Parameters Average
MonthlyWeekly
AverageMinimum Average
MonthlyWeekly
AverageInstant.
MaximumFlow (MGD) Report Report
Daily MaxXXX XXX XXX XXX pH (S.U.) XXX XXX 6.0 XXX XXX 9.0 Dissolved Oxygen XXX XXX 5.0 XXX XXX XXX Total Residual Chlorine XXX XXX XXX 0.4 XXX 1.3 CBOD5 May 1 - Oct 31 233 350 XXX 20 30 40 Nov 1 - Apr 30 292 467 XXX 25 40 50 Total Suspended Solids 350 525 XXX 30 45 60 Fecal Coliform (CFU/100 ml) May 1 - Sep 30 XXX XXX XXX 200
Geo MeanXXX 1,000 Oct 1 - Apr 30 XXX XXX XXX 2,000
Geo MeanXXX 10,000 Total Nitrogen XXX XXX XXX Report XXX XXX Ammonia-Nitrogen May 1 - Oct 31 52.5 XXX XXX 4.5 XXX 9.0 Nov 1 - Apr 30 158 XXX XXX 13.5 XXX 27 Total Phosphorus XXX XXX XXX Report XXX XXX Total Copper XXX XXX XXX Report XXX Report In addition, the permit contains the following major special conditions:
• Solids Management
• Whole Effluent Toxicity
• Requirements Applicable to Stormwater Outfalls
You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 814-332-6340.
The EPA Waiver is not in effect.
III. WQM Industrial Waste and Sewerage Applications under The Clean Streams Law
Southeast Region: Clean Water Program Manager, 2 East Main Street, Norristown, PA 19401.
WQM Permit No. 1513405, Sewage, Utilities Inc. of PA, P. O. Box 379, Dunkirk, MD 20754.
This proposed facility is located in West Bradford Township, Chester County.
Description of Action/Activity: Construction and operation of a pump station to service proposed 64 lot residential subdivision to discharge to ex gravity manhole.
WQM Permit No. 4613404, Sewage, Hatfield Township Municipal Authority, 3200 Advance Lane, Colmar, PA 18915-9766.
This proposed facility is located in Hatfield Township, Montgomery County.
Description of Action/Activity: Construction and operation of a sanitary pump station to serve assisted living community building.
WQM Permit No. 4605410, Sewage, Amendment, East Norriton Plymouth Whitpain Joint Sewer Authority, 200 Ross Street, Plymouth Meeting, PA 19462.
This proposed facility is located in Plymouth Township, Montgomery County.
Description of Action/Activity: Modifications and improvements to the treatment plant.
WQM Permit No. 4613405, Sewage, Lower Merion Township, 75 East Lancaster Avenue, Ardmore, PA 19003-2376.
This proposed facility Lower Merion Township, Montgomery County.
Description of Action/Activity: Construction and operation of a groundwater seep passive treatment system.
WQM Permit No. 1513406, Sewage, Camphill Soltane, 224 Nantmeal Road, Glenmoore, PA 19343.
This proposed facility is located in East Nantmeal Township, Chester County.
Description of Action/Activity: Construction of a conveyance and community sewer treatment system.
Southcentral Region: Clean Water Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110. Phone: 717-705-4707.
WQM Permit No. 2895201, Transfer #1, Sewerage, AE Sauce, Inc. dba Gibble Foods, 357 West Main Avenue, Myerstown, PA 17067.
This proposed facility is located in Antrim Township, Franklin County.
Description of Proposed Action/Activity: Seeking approval for transfer of permit.
WQM Permit No. 3693401, Amendment 13-1, Sewerage, Millersville Borough, 100 Municipal Drive, Millersville, PA 17551.
This proposed facility is located in Manor Township, Lancaster County.
Description of Proposed Action/Activity: Seeking permit approval for the improvements / replacement of blowers.
Southwest Region: Water Management Program Manager, 400 Waterfront Drive, Pittsburgh, PA 15222-4745
WQM Permit No. 3013401, Sewerage, Morris Twp, 1317 Browns Crk Rd., Sycamore, PA 15364
This proposed facility is located in Morris Twp, Greene Cnty
Description of Proposed Action/Activity: Application for the construction and operation of an STP.
Northwest Region: Clean Water Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481
WQM Permit No. WQG01371301, Sewage, Nathaniel D. Hunter, 620 Wilson Mill Road, New Castle, PA 16105.
This proposed facility is located in Wilmington Township, Lawrence County.
Description of Proposed Action/Activity: Single Residence Sewage Treatment Plant.
WQM Permit No. WQG018709, Sewage, Ronald W. Sevin, 7775 Route 6N, Edinboro, PA 16412.
This existing facility is located in Elk Creek Township, Erie County.
Description of Proposed Action/Activity: Transfer of an existing Single Residence Sewage Treatment Plant.
WQM Permit No. WQG018768, Sewage, Brian M. & Christine L. Turner, 15303 Ridge Road, Meadville, PA 16335.
This existing facility is located in Hayfield Township, Crawford County.
Description of Proposed Action/Activity: Transfer of an existing Single Residence Sewage Treatment Plant.
WQM Permit No. 2513402, Sewage, Young Men's Christian Association of Youngstown Ohio, 17 North Champion Street, P.O. Box 1287, Youngstown, OH 44501-1287.
This proposed facility is located in Springfield Township, Erie County.
Description of Proposed Action/Activity: Application to replace existing wastewater treatment facility with new, high capacity plant.
WQM Permit No. 2013201, Industrial Waste, Apple Shamrock Dairy Farms, LLC, 32821 Guys Mills Road, Townville, PA 16360.
This proposed facility is located in Steuben Township, Crawford County.
Description of Proposed Action/Activity: Application for construction of dairy facilities and manure storage ponds.
WQM Permit No. 2578404, Sewage, Albion Assembly of God, P.O. Box 55, Albion, PA 16401.
This existing facility is located in Conneaut Township, Erie County.
Description of Proposed Action/Activity: Transfer of an existing permit for a small flow treatment facility.
IV. NPDES Applications for Stormwater Discharges from MS4
Southeast Region: Clean Water Program Manager, 2 East Main Street, Norristown, PA 19401
PAI130542, MS4, Upper Providence Township Delaware County, 935 N. Providence Road, Media, PA 19063. The application is for a renewal of an individual NPDES permit for the discharge of stormwater from a regulated municipal separate storm sewer system (MS4) to waters of the Commonwealth in Upper Providence Township, Delaware County. The receiving stream(s), Unnamed Tributary of Crum Creek, Unnamed Tributary of Ridley Creek, are located in State Water Plan watershed 3G and are classified for Warm Water Fishes, Migratory Fishes, High Quality Waters—Trout Stocking, Trout Stocking, aquatic life, water supply and recreation.
The Department has made a tentative determination to issue the NPDES permit. Written comments on the application and draft permit will be accepted for 30 days following publication of this notice. The period for comment may be extended at the discretion of DEP for one additional 15-day period. You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 484-250-5910.
The EPA waiver is not in effect.
PAI130021, MS4, Marple Township Delaware County, 227 S Sproul Road, Broomall, PA 19008. The application is for a new individual NPDES permit for the discharge of stormwater from a regulated municipal separate storm sewer system (MS4) to waters of the Commonwealth in Marple Township, Delaware County. The receiving stream(s), Crum Creek, Darby Creek, Hotland Run, Langford Run, Trout Run, Unnamed Tributary to Crum Creek and Whetstone Run, is located in State Water Plan watershed 3-G and is classified for Warm Water Fishes, Migratory Fishes, Trout Stocking and Migratory Fishes, aquatic life, water supply and recreation.
The Department has made a tentative determination to issue the NPDES permit. Written comments on the application and draft permit will be accepted for 30 days following publication of this notice. The period for comment may be extended at the discretion of DEP for one additional 15-day period. You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 484-250-5910.
The EPA waiver is not in effect.
Southcentral Region: Clean Water Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110. Telephone: 717-705-4707.
PAI133513, MS4, Hampden Township Cumberland County, 230 S Sporting Hill Road, Mechanicsburg, PA 17050-3097. The application is for a renewal of an individual NPDES permit for the discharge of stormwater from a regulated municipal separate storm sewer system (MS4) to waters of the Commonwealth in Hampden Township, Cumberland County. The receiving stream(s), Conodoguinet Creek, Pine Run, Sears Run, Trindle Spring Run, Unnamed Tributary to Cedar Run, Unnamed Tributary to Conodoguinet Creek and Unnamed Tributary to Trindle Spring Run, is located in State Water Plan watershed 7-B and 7-E and is classified for Warm Water Fishes, Migratory Fishes, High Quality Waters—Cold Water Fishes, Cold Water Fishes and Migratory Fishes, aquatic life, water supply and recreation.
The Department has made a tentative determination to issue the NPDES permit. Written comments on the application and draft permit will be accepted for 30 days following publication of this notice. The period for comment may be extended at the discretion of DEP for one additional 15-day period. You may make an appointment to review the DEP files on this case by calling the File Review Coordinator at 717-705-4732.
The EPA waiver is not in effect.
V. Applications for NPDES Waiver Stormwater Discharges from MS4
Southcentral Region: Clean Water Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110. Telephone: 717-705-4707
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAG133514 Marion Township
420 Water Street
Womelsdorf, PA 19567
Berks Marion Township Tulpehocken Creek/ TSF, MF
VI. NPDES Individual Permit Applications for Discharges of Stormwater Associated with Construction Activities
Northeast Region: Watershed Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18701-1915.
Northampton County Conservation District: 14 Gracedale Ave., Greystone Building, Nazareth, PA 18064, 610-746-1971.
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI024813003 Michael Gamzon
Riverbend Hanover Properties LLC
1 Rockefeller Plaza
Suite 2301
New York, NY 10020
Northampton Hanover Twp. And East Allen Twp. Monocacy Creek,
(HQ-CWF, MF)Susquehanna County Conservation District: 88 Chenango Street, Montrose, Pa 18801, 570-278-4600, x 280
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI025813001 Leatherstocking Gas Company, Inc.
49 Court Street
Binghamton, NY 13902
Susquehanna Bridgewater Township Meshoppen Creek, CWF, MF
Snake Creek
CWF, MF
Lake Montrose
CWF, MFSouthcentral Region: Waterways & Wetlands Program, 909 Elmerton Avenue, Harrisburg, PA 17110-8200, 717.705.4802
Permit # Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI032113003 Rostan Associates
415 Fallowfield Road
Camp Hill, PA 17011
Cumberland Middlesex Township Letort Spring Run
(HQ-CWF)PAI032113004 RE Invest Tire and Wheel Renewal, LLC
1855 New Highway, Suite C
Farmingdal, NY 11735
Cumberland Carlisle Borough Letort Spring Run
(HQ-CWF, MF)Northcentral Region: Waterways & Wetlands Program Manager, 208 West Third Street, Williamsport, PA 17701
Centre County Conservation District: 414 Holmes Avenue, Suite 4, Bellefonte, PA 16823, (814) 355-6817
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI041413002 Logistics Group Inc Centre Patton Township UNT to Buffalo Run
HQ-CWFPotter County Conservation District: 107 Market Street, Coudersport, PA 16915 (814) 274-8411, X 4
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI045313003 Gold Church
35 PA Route 44A
Genesee PA
Potter Ulysess Township Middle Branch Genesee
HQ-CWF
VII. List of NOIs for NPDES and/or Other General Permit Types
PAG-12 CAFOs
CAFO Notices of Intent Received
Southcentral Region: Clean Water Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110. Telephone: 717-705-4707.
PAG123608, CAFO, Irvin G. Weaver, 6 Witman Road, Womelsdorf, PA 19567.
This proposed facility is located in Tulpehocken Township, Berks County.
Description of Size and Scope of Proposed Operation/Activity: PAG-12 renewal application for an existing poultry operation.
The receiving stream, Little Swatara Creek, is in watershed 7-D, and classified for: CWF.
The proposed effluent limits for the operation/activity include: Except for the chronic or catastrophic rainfall events defined as over the 25-year/24-hour rain storms, the CAFO general permit is a non-discharge NPDES permit. Where applicable, compliance with 40 CFR federal effluent limitation guidelines is required. The general permit requires no other numeric effluent limitations and compliance with the Pennsylvania Nutrient Management Act and the Clean Stream Law constitutes compliance with the state narrative water quality standards.
PAG123607, CAFO, Randall J. Weaver, 8 Witman Road, Womelsdorf, PA 19567.
This proposed facility is located in Marion Township, Berks County.
Description of Size and Scope of Proposed Operation/Activity: PAG-12 renewal application for an existing poultry operation.
The receiving stream, UNT Tulpehocken Creek, is in watershed 3-C, and classified for: TSF.
The proposed effluent limits for the operation/activity include: Except for the chronic or catastrophic rainfall events defined as over the 25-year/24-hour rain storms, the CAFO general permit is a non-discharge NPDES permit. Where applicable, compliance with 40 CFR federal effluent limitation guidelines is required. The general permit requires no other numeric effluent limitations and compliance with the Pennsylvania Nutrient Management Act and the Clean Stream Law constitutes compliance with the state narrative water quality standards.
Northcentral Region: Clean Water Program Manager, 208 West Third Street, Williamsport, PA 17701
NPDES Permit No. PAG124846, CAFO, Country View Family Farms, LLC, 1301 Fulling Mill Road, Middletown, PA 17057.
This existing facility is located in Sullivan Township, Tioga County.
Description of size and scope of proposed operation/activity: The facility is comprised of approximately 5,000 Sows, 960 Sows with litters, 12 Boars, and 2,000 Gilts. There are a total of 2,746.60 AEUs.
The receiving stream, Unnamed Tributary to Corey Creek, is in watershed 4-A and classified for: Cold Water Fishes, Cold Water Fishes and Migratory Fishes. The proposed effluent limits for the operation/activity include: Except for the chronic or catastrophic rainfall events defined as over the 25-year/24-hour rain storms, the CAFO general permit is a non-discharge NPDES permit. Where applicable, compliance with 40 CFR federal effluent limitation guidelines is required. The general permit requires no other numeric effluent limitations and compliance with the Pennsylvania Nutrient Management Act and the Clean Stream Law constitutes compliance with the state narrative water quality standards.
[Continued on next Web Page]
No part of the information on this site may be reproduced for profit or sold for profit.This material has been drawn directly from the official Pennsylvania Bulletin full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.