§ 298.52. General facility standards.
(a) Preparedness and prevention. The owner and operator of a waste oil processor or rerefiners facility shall comply with the following requirements:
(1) Maintenance and operation of facility. A facility shall be maintained and operated to minimize the possibility of a fire, explosion or any unplanned sudden or nonsudden release of waste oil to air, soil or surface water which could threaten human health or the environment.
(2) Required equipment. A facility shall be equipped with the following, unless none of the hazards posed by waste oil handled at the facility could require a particular kind of equipment specified in subparagraphs (i)(iv):
(i) An internal communications or alarm system capable of providing immediate emergency instruction (voice or signal) to facility personnel.
(ii) A device, such as a telephone (immediately available at the scene of operations) or a hand-held two-way radio, capable of summoning emergency assistance from local police departments, fire departments or State or local emergency response teams.
(iii) A portable fire extinguisher, fire control equipment (including special extinguishing equipment, such as that using foam, inert gas or dry chemicals), spill control equipment and decontamination equipment.
(iv) Water at adequate volume and pressure to supply water hose streams, foam producing equipment, or automatic sprinklers or water spray systems.
(3) Testing and maintenance of equipment. The facility communications or alarm systems, fire protection equipment, spill control equipment and decontamination equipment, when required, shall be tested and maintained as necessary to assure its proper operation in time of emergency.
(4) Access to communications or alarm system.
(i) Whenever waste oil is being poured, mixed, spread or otherwise handled, the personnel involved in the operation shall have immediate access to an internal alarm or emergency communication device, either directly or through visual or voice contact with another employee, unless the device is not required in paragraph (2).
(ii) When there is just one employee on the premises while the facility is operating, the employee shall have immediate access to a device, such as a telephone (immediately available at the scene of operation) or a hand-held two-way radio, capable of summoning external emergency assistance, unless the device is not required in paragraph (2).
(5) Required aisle space. The owner or operator shall maintain aisle space to allow the unobstructed movement of personnel, fire protection equipment, spill control equipment and decontamination equipment to any area of facility operation in an emergency, unless aisle space is not needed for any of these purposes.
(6) Arrangements with local authorities.
(i) The owner or operator shall attempt to make the following arrangements, as appropriate, for the type of waste oil handled at the facility and the potential need for the services of these organizations:
(A) Arrangements to familiarize police, fire departments and emergency response teams with the layout of the facility, properties of waste oil handled at the facility and associated hazards, places where facility personnel would normally be working, entrances to roads inside the facility and possible evacuation routes.
(B) Where more than one police and fire department might respond to an emergency, agreements designating primary emergency authority to a specific police and a specific fire department and agreements with any others to provide support to the primary emergency authority.
(C) Agreements with State emergency response teams, emergency response contractors and equipment suppliers.
(ii) Arrangements to familiarize local hospitals with the properties of waste oil handled at the facility and the types of injuries or illnesses which could result from fires, explosions or releases at the facility.
(iii) If State or local authorities decline to enter into these arrangements, the owner or operator shall document the refusal in the operating record.
(b) Contingency plan and emergency procedures. Owners and operators of waste oil processing and rerefining facilities shall comply with the following requirements:
(1) Purpose and implementation of contingency plan.
(i) Each owner or operator shall have a contingency plan for the facility. The contingency plan shall be designed to minimize hazards to human health or the environment from fires, explosions or any unplanned sudden or nonsudden release of waste oil to air, soil or surface water.
(ii) The provisions of the plan shall be carried out immediately whenever there is a fire, explosion or release of waste oil which could threaten human health or the environment.
(2) Content of contingency plan.
(i) The contingency plan shall describe the actions facility personnel shall take to comply with paragraphs (1) and (6) in response to fires, explosions or any unplanned sudden or nonsudden release of waste oil to air, soil or surface water at the facility.
(ii) If the owner or operator has already complied with 40 CFR Part 264, Subparts C and D (relating to preparedness and prevention; and contingency plan and emergency procedures), incorporated by reference in § 264a.1 (relating to incorporation by reference, purpose, scope and reference), and modified in § 264a.56 (relating to emergency procedures) or has already prepared some other emergency or contingency plan, the owner or operator need only amend that plan to incorporate waste oil management provisions that are sufficient to comply with this chapter.
(iii) The plan shall describe arrangements agreed to by local police departments, fire departments, hospitals, contractors and State and local emergency response teams to coordinate emergency services, under subsection (a)(6).
(iv) The plan shall list names, addresses and the office and home phone numbers of the persons qualified to act as emergency coordinators, as described in paragraph (5), and this list shall be kept up to date. If more than one person is listed, one person shall be named as primary emergency coordinator and the others shall be listed in the order in which they will assume responsibility as alternates.
(v) The plan shall include a list of all emergency equipment at the facilitysuch as fire extinguishing systems, spill control equipment, communications and alarm systems (internal and external) and decontamination equipmentif this equipment is required. This list shall be kept up to date. In addition, the plan shall include the location and a physical description of each item on the list, and a brief outline of its capabilities.
(vi) The plan shall include an evacuation plan for facility personnel if there is a possibility that evacuation could be necessary. This plan shall describe signals to be used to begin evacuation, evacuation routes and alternate evacuation routes, in cases where the primary routes could be blocked by releases of waste oil or fires.
(3) Copies of contingency plan. A copy of the contingency plan and revisions to the plan shall be:
(i) Maintained at the facility.
(ii) Submitted to all local police departments, fire departments, hospitals and State and local emergency response teams that may be called upon to provide emergency services.
(4) Amendment of contingency plan. The contingency plan shall be reviewed and immediately amended, if necessary, whenever:
(i) Applicable regulations are revised.
(ii) The plan fails in an emergency.
(iii) The facility changes in its design, construction, operation, maintenance or other circumstances in a way that materially increases the potential for fires, explosions or releases of waste oil, or changes the response necessary in an emergency.
(iv) The list of emergency coordinators changes.
(v) The list of emergency equipment changes.
(5) Emergency coordinator. At all times, there shall be at least one employe either on the facility premises or on callfor example, available to respond to an emergency by reaching the facility within a short period of timewith the responsibility for coordinating all emergency response measures. This emergency coordinator shall be thoroughly familiar with all aspects of the facilitys contingency plan, the operations and activities at the facility, the location and characteristic of waste oil handled, the location of all records within the facility and facility layout. In addition, this person shall have the authority to commit the resources needed to carry out the contingency plan.
(6) Emergency procedures.
(i) Whenever there is an imminent or actual emergency situation, the emergency coordinator, or the designee when the emergency coordinator is on call, shall immediately do the following:
(A) Activate internal facility alarms or communication systems, if applicable, to notify all facility personnel.
(B) Notify appropriate State or local agencies with designated response roles if their help is needed.
(ii) Whenever there is a release, fire or explosion, the emergency coordinator shall immediately identify the character, exact source, amount and real extent of any released materials. The emergency coordinator may do this by observation or review of facility records of manifests and, if necessary, by chemical analysis.
(iii) Concurrently, the emergency coordinator shall assess possible hazards to human health or the environment that may result from the release, fire or explosion. This assessment shall consider both direct and indirect effects of the release, fire or explosion-for example, the effects of any toxic, irritating or asphyxiating gases that are generated or the effects of any hazardous surface water run-off from water or chemical agents used to control fire and heat-induced explosions.
(iv) If the emergency coordinator determines that the facility has had a release, fire or explosion which could threaten human health or the environment, outside the facility, the emergency coordinator shall report the findings as follows:
(A) If the assessment indicated that evacuation of local areas may be advisable, the emergency coordinator shall immediately notify the appropriate Departmental office of emergency response and the appropriate local authorities. The emergency coordinator shall be available to help appropriate officials decide whether local areas should be evacuated.
(B) The emergency coordinator shall immediately notify either the government official designated as the on-scene coordinator for the geographical area in the applicable regional contingency plan or the National Response Center (using the 24-hour toll free number (800) 424-8802). The report shall include:
(1) The name and telephone number of reporter.
(2) The name and address of the facility.
(3) The time and type of incident-for example, release or fire.
(4) The name and quantity of materials involved, to the extent known.
(5) The extent of injuries, if any.
(6) The possible hazards to human health, or the environment, outside the facility.
(v) During an emergency, the emergency coordinator shall take all reasonable measures necessary to ensure that fires, explosions and releases do not occur, recur or spread to other waste oil or hazardous waste at the facility. These measures shall include, if applicable, stopping processes and operation, collecting and containing released waste oil, and removing or isolating containers.
(vi) If the facility stops operation in response to a fire, explosion or release, the emergency coordinator shall monitor for leaks, pressure buildup, gas generation or ruptures in valves, pipes or other equipment, wherever this is appropriate.
(vii) Immediately after an emergency, the emergency coordinator shall provide for recycling, storing or disposing of recovered waste oil, contaminated soil or surface water, or any other material that results from a release, fire or explosion at the facility.
(viii) The emergency coordinator shall ensure that, in the affected areas of the facility, the following conditions apply:
(A) No waste or waste oil that may be incompatible with the released material is recycled, treated, stored or disposed of until cleanup procedures are completed.
(B) The emergency equipment listed in the contingency plan is cleaned and fit for its intended use before operations are resumed.
(C) The owner or operator shall notify the Department and applicable local authorities that the facility is in compliance with clauses (A) and (B) before operations are resumed in the affected areas of the facility.
(ix) The owner or operator shall note in the operating record the time, date and details of any incident that requires implementing the contingency plan. Within 15 days after the incident, the owner or operator shall submit a written report on the incident to the Department. The report shall include the following:
(A) The name, address and telephone number of the owner or operator.
(B) The name, address and telephone number of the facility.
(C) The date, time and type of incident-for example, fire or explosion.
(D) The name and quantity of materials involved.
(E) The extent of injuries, if any.
(F) An assessment of actual or potential hazards to human health or the environment, if applicable.
(G) An estimated quantity and disposition of recovered material that resulted from the incident.
Cross References This section cited in 25 Pa. Code § 298.57 (relating to operating record and reporting).