34 Pa. Code § 35.75. Sprinklers.

§ 35.75. Sprinklers.

 (a)  Quantity required. Booths 3 feet or more in width (measured along the floor or bottom of face), or having a face area of more than 16 square feet, shall be equipped with one or more approved automatic sprinklers. At least one automatic sprinkler shall be installed in booths between 3 feet and 8 feet in width, and one automatic sprinkler for each additional width of 8 feet or fraction thereof.

 (b)  Location in booths. Sprinklers shall be so located at the top of the booth that they do not readily become coated with paint or other materials, and in such position that they afford protection to some of the area outside and immediately adjacent to the face of the booth. No sprinklers shall be located less than 4 inches from the edge or the top of any booth. Each room booth shall be equipped with one approved automatic sprinkler for each 160 square foot unit of floor area or fraction thereof.

 (c)  Maintenance. The accumulated deposits of sprayed materials shall be cleaned from the sprinkler heads at frequent intervals with sufficient care to avoid injury to the sprinkler head.