Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 5598 (August 31, 2024).

34 Pa. Code § 39.185. Guarding live parts.

§ 39.185. Guarding live parts.

 (a)  Current-carrying parts of arresters on circuits above 750 volts, unless effectively isolated by elevation, shall be adequately guarded to protect persons from inadvertent contact with them, or from injury by arcing.

 (b)  Lightning arresters, unless provided with disconnectors, which are always opened before work is done on the arresters shall be so arranged that necessary adjustments are possible, without approach to current-carrying parts, through the use of permanently grounded mechanisms or suitable insulating appliances. If it is necessary that charging or adjustments be made with arresters alive, permanently grounded mechanisms or suitable insulating appliances shall always be provided.

 (c)  Guarding shall comply with § §  39.105 and 39.143 (relating to guarding live parts; isolation by elevation).

Cross References

   This section cited in 34 Pa. Code §  39.201 (relating to storage batteries, transformers and lightning arresters).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.