34 Pa. Code § 3a.33. Explosion doors.

§ 3a.33. Explosion doors.

 Stoker coal fired boilers under positive pressure must be equipped with explosion doors to relieve furnace pressure. The explosion doors must be located in the setting wall within 7 feet of the firing floor or any platform, and must be provided with substantial deflectors to divert the blast away from personnel.