Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 5598 (August 31, 2024).

34 Pa. Code § 50.28. Horizontal exits.

§ 50.28. Horizontal exits.

 (a)  A horizontal exit is a 2-hour fire wall with one or more openings protected by 1 1/2-hour door assemblies which permit passage from one building or structure to another or area of refuge within the same building.

 (b)  Horizontal exits may constitute no more than 50% of the required units of exit.

 (c)  Fire walls which serve as horizontal exits shall extend to exterior walls or 2-hour fire walls. They shall not be dependent on any structural members of less than 2-hour fireresistance.

 (d)  A horizontal exit shall have at least one door which swings with the exit travel from each building section that it serves.

Cross References

   This section cited in 34 Pa. Code §  51.28 (relating to horizontal exits); 34 Pa. Code §  52.28 (relating to horizontal exits); 34 Pa. Code §  53.28 (relating to horizontal exits); 34 Pa. Code §  54.28 (relating to horizontal exits); 34 Pa. Code §  55.28 (relating to horizontal exits); 34 Pa. Code §  56.28 (relating to horizontal exits); 34 Pa. Code §  58.28 (relating to horizontal exits); and 34 Pa. Code §  59.28 (relating to horizontal exits).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.