§ 50.91. High rise building.
(a) A high rise building is a building that has an exterior face which exceeds 75 feet when measured from ground level to five feet above the highest occupiable floor level.
(b) High rise buildings shall be totally protected with an automatic sprinkler system.
(c) Travel distance may be increased to the following in buildings totally protected by an automatic sprinkler system installed in accordance with NFPA-13, 1983 Edition:
(1) Two hundred feet from any point to an exit.
(2) Three hundred feet between exits.
(3) One hundred feet from dead ends and areas with a single path of egress.
(d) Interior finish requirements may be reduced by one class in buildings totally protected by an automatic sprinkler system.
(e) A dry standpipe system shall be required for high rise buildings. The dry standpipe system shall comply with the regulations for Class I service as listed in NFPA-14, 1980 Edition.
Notes of Decisions Automatic Sprinklers
The regulations exempt cities of the first class from complying with Chapters 4959, which require high rise buildings to have an automatic sprinkler system. A city of the first class has a population of 1 million or more under 53 P. S. § 101. Because Philadelphia was a city of the first class the city was not bound by the Pennsylvania Code provisions. In re One Meridian Plaza Fire Litig., No. 91-2171 Consolidated with Nos. 91-2172, 91-2226, 91-2227, 91-2374, 91-2545, 91-2546, 91-2547, 1994 U. S. Dist. LEXIS 4343 (E. D. Pa. April 6, 1994), summary judgment denied, No. 91-2171, 1994 U. S. Dist. LEXIS 5532, Prod. Liab. Rep. (CCH) para. 13918 (E. D. Pa. April 29, 1994).
No part of the information on this site may be reproduced for profit or sold for profit.
This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.