§ 53.22. Travel distance to exits.
(a) Exits shall be so arranged that the total length of travel from any point to reach an exit shall not exceed 150 feet. Exits shall be so arranged that one exit is not more than 200 feet from another exit. Dead ends and occupancy areas with a single path of egress travel should be eliminated where possible, but in no case shall any of these occupancy areas be more than 75 feet from an exit.
(b) Travel distance may be increased to the following in buildings totally protected by an automatic sprinkler system:
(1) Two hundred feet from any point to an exit.
(2) Three hundred feet between exits.
(3) One hundred feet for dead ends and areas with a single path of egress.