Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 5598 (August 31, 2024).

34 Pa. Code § 57.2. Separation and mixed occupancy.

§ 57.2. Separation and mixed occupancy.

 When a C-4 occupancy shares a structure with one or more occupancies, the structure shall be governed in one of the following manners:

   (1)  C-4 occupancies shall be separated from all A-1, A-2, B, C-1, C-3 and C-5 occupancies by fire walls. Each portion thus separated shall be considered a separate building.

   (2)  C-4 occupancies may be separated from A-3, C-2 and D-O occupancies by fire walls and considered separate buildings, or C-4 occupancies may share a building with A-3, C-2 or D-O occupancies as a mixed occupancy when all of the following conditions are met:

     (i)   The construction type complies with the most restrictive limitations of all divisions occupying the building.

     (ii)   The building size limitations and story height limitations do not exceed the C-4 requirements.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.