Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 6234 (September 28, 2024).

55 Pa. Code § 6400.111. Fire extinguishers.

§ 6400.111. Fire extinguishers.

 (a)  There shall be at least one operable fire extinguisher with a minimum 2-A rating for each floor, including the basement and attic.

 (b)  If the indoor floor area on a floor including the basement or attic is more than 3,000 square feet, there shall be an additional fire extinguisher with a minimum 2-A rating for each additional 3,000 square feet of indoor floor space.

 (c)  A fire extinguisher with a minimum 2A-10BC rating shall be located in each kitchen. The kitchen extinguisher meets the requirements for one floor as required in subsection (a).

 (d)  A fire extinguisher shall be listed by Underwriters Laboratories or approved by Factory Mutual Systems.

 (e)  A fire extinguisher shall be accessible to staff persons and individuals.

 (f)  A fire extinguisher shall be inspected and approved annually by a fire safety expert. The date of the inspection shall be on the extinguisher.

Source

   The provisions of this §  6400.111 adopted August 9, 1991, effective November 8, 1991, 21 Pa.B. 3595.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.