§ 39.106. Isolating live parts by elevation.
Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:
Voltage of Conductors Elevation (in feet) 300750 7 7502,500 7 2,5007,500 8 7,50030,000 9 30,00070,000 10 70,000100,000 12 Over 100,000 14
Cross References This section cited in 34 Pa. Code § 39.143 (relating to isolation by elevation); 34 Pa. Code § 39.160 (relating to guarding live parts of switches and automatic cut-outs not installed on switchboards); and 34 Pa. Code § 39.199 (relating to guarding or isolating live parts).