Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 5598 (August 31, 2024).

34 Pa. Code § 39.106. Isolating live parts by elevation.

§ 39.106. Isolating live parts by elevation.

 Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:

Voltage of ConductorsElevation (in feet)
300—750 7
750—2,500 7
2,500—7,500 8
7,500—30,000 9
30,000—70,00010
70,000—100,00012
Over 100,00014

Cross References

   This section cited in 34 Pa. Code §  39.143 (relating to isolation by elevation); 34 Pa. Code §  39.160 (relating to guarding live parts of switches and automatic cut-outs not installed on switchboards); and 34 Pa. Code §  39.199 (relating to guarding or isolating live parts).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.