Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 5598 (August 31, 2024).

34 Pa. Code § 39.125. Guarding live parts in battery room.

§ 39.125. Guarding live parts in battery room.

 (a)  The arrangement of cells and connections shall be such that no two current-carrying parts between which a voltage exceeding 150 exists, shall be closer than three feet, if the parts are so exposed that persons are liable to make accidental contact with both at the same time.

 (b)  No conductor above 150 volts to ground shall be placed in any passageway, unless guarded or isolated by elevation.

Cross References

   This section cited in 34 Pa. Code §  39.85 (relating to general requirements); 34 Pa. Code §  39.121 (relating to applicability); and 34 Pa. Code §  39.201 (relating to storage batteries, transformers, and lightning arresters).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.