Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 5598 (August 31, 2024).

34 Pa. Code § 39.216. Precautions to avoid excessive inductance and eddy currents.

§ 39.216. Precautions to avoid excessive inductance and eddy currents.

 Supply conductors of alternating-current or direct-current circuits should not be run in separate iron conduits or on opposite sides of I beams or other iron structures or be otherwise run so as to increase abnormally the self-inductance of the circuit. Such construction, by introducing large self inductance in direct-current circuits, causes fuses to blow explosively; in alternating-current circuits it causes heating due to eddy currents in the metal.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.